Softwell Digital Practical Manual
Practical 01 - Create Operator Terminal Project
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, HMI target/simulator, PLC communication settings
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Create Operator Terminal Project.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Create Operator Terminal Project | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Create Operator Terminal Project is completed, verified and documented inside the EcoStruxure Operator Terminal HMI Manual workflow.
Talk to Automation Advisor
Get expert guidance for course selection, corporate training, project support and practical learning path.
Softwell Digital Practical Manual
Practical 02 - Select HMI Model
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, HMI target/simulator, PLC communication settings
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Select HMI Model.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Select HMI Model | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Select HMI Model is completed, verified and documented inside the EcoStruxure Operator Terminal HMI Manual workflow.
Skills & Tools You Will Learn
Important automation skills are arranged for job-level, project-level and Industry 4.0 learning.
Softwell Digital Practical Manual
Practical 03 - Configure PLC Driver
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, HMI target/simulator, PLC communication settings
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Configure PLC Driver.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Configure PLC Driver | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Configure PLC Driver is completed, verified and documented inside the EcoStruxure Operator Terminal HMI Manual workflow.
Softwell Digital Practical Manual
Practical 04 - Create Tag Database
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, HMI target/simulator, PLC communication settings
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Create Tag Database.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Create Tag Database | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Create Tag Database is completed, verified and documented inside the EcoStruxure Operator Terminal HMI Manual workflow.
Why Choose Softwell Automation
Learn automation with practical examples, industrial troubleshooting approach and complete IT/OT learning path.
Softwell Digital Practical Manual
Practical 05 - Create Main Screen
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, HMI target/simulator, PLC communication settings
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Create Main Screen.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Create Main Screen | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Create Main Screen is completed, verified and documented inside the EcoStruxure Operator Terminal HMI Manual workflow.
Course Contents / Curriculum
The curriculum follows a practical sequence from fundamentals to project integration.
Softwell Digital Practical Manual
Practical 06 - Add Push Button Object
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, HMI target/simulator, PLC communication settings
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Add Push Button Object.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Add Push Button Object | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Add Push Button Object is completed, verified and documented inside the EcoStruxure Operator Terminal HMI Manual workflow.
Frequently Asked Questions About EcoStruxure Operator Terminal HMI Manual Operator Terminal HMI Practical Manual
Who can join this training?
Students, freshers, working engineers, maintenance teams and corporate plant engineers can join based on their requirement.
Is practical training included?
Yes. The training is focused on PLC, SCADA, HMI, VFD, communication, troubleshooting and project based practice.
Can I request online or corporate training?
Yes. Softwell Automation provides classroom, online, corporate and in-plant training options.
Softwell Digital Practical Manual
Practical 07 - Add Pilot Lamp Object
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, HMI target/simulator, PLC communication settings
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Add Pilot Lamp Object.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Add Pilot Lamp Object | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Add Pilot Lamp Object is completed, verified and documented inside the EcoStruxure Operator Terminal HMI Manual workflow.
Softwell Digital Practical Manual
Practical 08 - Add Numeric Display
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, HMI target/simulator, PLC communication settings
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Add Numeric Display.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Add Numeric Display | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Add Numeric Display is completed, verified and documented inside the EcoStruxure Operator Terminal HMI Manual workflow.
Softwell Digital Practical Manual
Practical 09 - Add Numeric Entry
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, HMI target/simulator, PLC communication settings
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Add Numeric Entry.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Add Numeric Entry | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Add Numeric Entry is completed, verified and documented inside the EcoStruxure Operator Terminal HMI Manual workflow.
Softwell Digital Practical Manual
Practical 10 - Motor Control Screen
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, HMI target/simulator, PLC communication settings
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Motor Control Screen.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Motor Control Screen | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Motor Control Screen is completed, verified and documented inside the EcoStruxure Operator Terminal HMI Manual workflow.
Softwell Digital Practical Manual
Practical 11 - Alarm Banner Setup
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, HMI target/simulator, PLC communication settings
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Alarm Banner Setup.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Alarm Banner Setup | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Alarm Banner Setup is completed, verified and documented inside the EcoStruxure Operator Terminal HMI Manual workflow.
Softwell Digital Practical Manual
Practical 12 - Alarm History Screen
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, HMI target/simulator, PLC communication settings
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Alarm History Screen.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Alarm History Screen | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Alarm History Screen is completed, verified and documented inside the EcoStruxure Operator Terminal HMI Manual workflow.
Softwell Digital Practical Manual
Practical 13 - Trend Screen Setup
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, HMI target/simulator, PLC communication settings
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Trend Screen Setup.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Trend Screen Setup | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Trend Screen Setup is completed, verified and documented inside the EcoStruxure Operator Terminal HMI Manual workflow.
Softwell Digital Practical Manual
Practical 14 - Recipe Screen Practical
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, HMI target/simulator, PLC communication settings
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Recipe Screen Practical.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Recipe Screen Practical | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Recipe Screen Practical is completed, verified and documented inside the EcoStruxure Operator Terminal HMI Manual workflow.
Softwell Digital Practical Manual
Practical 15 - User Security Setup
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, HMI target/simulator, PLC communication settings
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for User Security Setup.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | User Security Setup | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
User Security Setup is completed, verified and documented inside the EcoStruxure Operator Terminal HMI Manual workflow.
Softwell Digital Practical Manual
Practical 16 - Screen Navigation
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, HMI target/simulator, PLC communication settings
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Screen Navigation.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Screen Navigation | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Screen Navigation is completed, verified and documented inside the EcoStruxure Operator Terminal HMI Manual workflow.
Softwell Digital Practical Manual
Practical 17 - Runtime Simulation
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, HMI target/simulator, PLC communication settings
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Runtime Simulation.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Runtime Simulation | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Runtime Simulation is completed, verified and documented inside the EcoStruxure Operator Terminal HMI Manual workflow.
Softwell Digital Practical Manual
Practical 18 - Download to HMI
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, HMI target/simulator, PLC communication settings
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Download to HMI.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Download to HMI | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Download to HMI is completed, verified and documented inside the EcoStruxure Operator Terminal HMI Manual workflow.
Softwell Digital Practical Manual
Practical 19 - Communication Diagnostics
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, HMI target/simulator, PLC communication settings
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Communication Diagnostics.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Communication Diagnostics | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Communication Diagnostics is completed, verified and documented inside the EcoStruxure Operator Terminal HMI Manual workflow.
Softwell Digital Practical Manual
Practical 20 - Final Operator Terminal HMI Project
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, HMI target/simulator, PLC communication settings
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Final Operator Terminal HMI Project.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Final Operator Terminal HMI Project | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Final Operator Terminal HMI Project is completed, verified and documented inside the EcoStruxure Operator Terminal HMI Manual workflow.
Before You Start: Prerequisites, Tested Version, Safety and Evidence
This manual is a practical training workbook, not a substitute for the installed product manual or the site's approved engineering procedure. Record the exact software, firmware, license and hardware before following a step because menus and supported functions can vary by release.
Tested-version planning scope: Confirm operator-terminal software Version 3.x or the installed release, target firmware, communication driver and runtime license. Enter the exact lab-tested software, firmware and hardware in the record below before course delivery; never assume cross-version compatibility.
Software build, firmware, device catalog, driver, communication interface and license status.
Use an isolated training system. Follow electrical, mechanical, process and cybersecurity controls before energizing or downloading.
Keep the source project, parameter/code export, screenshot/trend, fault test, correction and final pass result.
Last reviewed by Softwell Automation Technical Training Team on 17 July 2026.
| Field | Learner record | Verification |
|---|---|---|
| Software / firmware | ________________ | Matches the training device and official compatibility information |
| Project / backup | ________________ | Saved before and after the practical |
| Pass evidence | ________________ | Runtime value, trend, alarm, diagnostic or report attached |
| Fault tested | ________________ | Symptom, cause, check and corrective action documented |
Practice, Viva and Extension Challenge
Change one approved input or parameter, predict the result, execute the test and explain any difference.
Explain the data flow, safety boundary, first diagnostic check and recovery method without opening the answer.
Add one useful function while preserving the original pass criteria, alarm behavior and rollback path.
Combine at least three practicals, submit a versioned project and evidence pack, and demonstrate repeatable recovery.
Content status: Substantively reviewed and expanded 17 July 2026. Verify release-specific details against the linked official documentation.