FactoryTalk View SE Manual
Site Edition SCADA Practical Manual

Official Philosophy: Open the software, open the Softwell Notebook, and perform the practical.

20 Matching Lab Practicals
Action Flow Manual
No Theory / Only Practical
Softwell Training Template

Softwell
Digital Practical
Notebook

[check] Open -> Click -> Select -> Download -> Test -> Complete

NO THEORY * ONLY PRACTICAL
P01

Softwell Digital Practical Manual

Practical 01 - Create SE Application

Philosophy: Open the software, open the Softwell manual, and perform the practical.

FactoryTalk View SESCADAHMIAlarms
Software: FactoryTalk View Studio SE, FactoryTalk Linx, SE Client / Runtime
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
01
STEP 01
Open FactoryTalk View Studio SE and load the training project for FactoryTalk View SE Manual.
v
02
STEP 02
Create or open the practical object for Create SE Application.
v
03
STEP 03
Configure the required tags, parameters, blocks or screen objects for this FactoryTalk View SE workflow.
v
04
STEP 04
Run compile, simulation, runtime or online monitoring as applicable and verify the practical behavior.
v
05
STEP 05
Save the work, record the result and tick Practical Create SE Application as complete.

Expected Result

Create SE Application is completed, verified and documented inside the FactoryTalk View SE Manual workflow.

P02

Softwell Digital Practical Manual

Practical 02 - Set FactoryTalk Directory

Philosophy: Open the software, open the Softwell manual, and perform the practical.

FactoryTalk View SESCADAHMIAlarms
Software: FactoryTalk View Studio SE, FactoryTalk Linx, SE Client / Runtime
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
01
STEP 01
Open FactoryTalk View Studio SE and load the training project for FactoryTalk View SE Manual.
v
02
STEP 02
Create or open the practical object for Set FactoryTalk Directory.
v
03
STEP 03
Configure the required tags, parameters, blocks or screen objects for this FactoryTalk View SE workflow.
v
04
STEP 04
Run compile, simulation, runtime or online monitoring as applicable and verify the practical behavior.
v
05
STEP 05
Save the work, record the result and tick Practical Set FactoryTalk Directory as complete.

Expected Result

Set FactoryTalk Directory is completed, verified and documented inside the FactoryTalk View SE Manual workflow.

P03

Softwell Digital Practical Manual

Practical 03 - Add FactoryTalk Linx Shortcut

Philosophy: Open the software, open the Softwell manual, and perform the practical.

FactoryTalk View SESCADAHMIAlarms
Software: FactoryTalk View Studio SE, FactoryTalk Linx, SE Client / Runtime
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
01
STEP 01
Open FactoryTalk View Studio SE and load the training project for FactoryTalk View SE Manual.
v
02
STEP 02
Create or open the practical object for Add FactoryTalk Linx Shortcut.
v
03
STEP 03
Configure the required tags, parameters, blocks or screen objects for this FactoryTalk View SE workflow.
v
04
STEP 04
Run compile, simulation, runtime or online monitoring as applicable and verify the practical behavior.
v
05
STEP 05
Save the work, record the result and tick Practical Add FactoryTalk Linx Shortcut as complete.

Expected Result

Add FactoryTalk Linx Shortcut is completed, verified and documented inside the FactoryTalk View SE Manual workflow.

P04

Softwell Digital Practical Manual

Practical 04 - Create HMI Tags

Philosophy: Open the software, open the Softwell manual, and perform the practical.

FactoryTalk View SESCADAHMIAlarms
Software: FactoryTalk View Studio SE, FactoryTalk Linx, SE Client / Runtime
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
01
STEP 01
Open FactoryTalk View Studio SE and load the training project for FactoryTalk View SE Manual.
v
02
STEP 02
Create or open the practical object for Create HMI Tags.
v
03
STEP 03
Configure the required tags, parameters, blocks or screen objects for this FactoryTalk View SE workflow.
v
04
STEP 04
Run compile, simulation, runtime or online monitoring as applicable and verify the practical behavior.
v
05
STEP 05
Save the work, record the result and tick Practical Create HMI Tags as complete.

Expected Result

Create HMI Tags is completed, verified and documented inside the FactoryTalk View SE Manual workflow.

P05

Softwell Digital Practical Manual

Practical 05 - Create Main Graphic Display

Philosophy: Open the software, open the Softwell manual, and perform the practical.

FactoryTalk View SESCADAHMIAlarms
Software: FactoryTalk View Studio SE, FactoryTalk Linx, SE Client / Runtime
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
01
STEP 01
Open FactoryTalk View Studio SE and load the training project for FactoryTalk View SE Manual.
v
02
STEP 02
Create or open the practical object for Create Main Graphic Display.
v
03
STEP 03
Configure the required tags, parameters, blocks or screen objects for this FactoryTalk View SE workflow.
v
04
STEP 04
Run compile, simulation, runtime or online monitoring as applicable and verify the practical behavior.
v
05
STEP 05
Save the work, record the result and tick Practical Create Main Graphic Display as complete.

Expected Result

Create Main Graphic Display is completed, verified and documented inside the FactoryTalk View SE Manual workflow.

P06

Softwell Digital Practical Manual

Practical 06 - Add Numeric Display and Entry

Philosophy: Open the software, open the Softwell manual, and perform the practical.

FactoryTalk View SESCADAHMIAlarms
Software: FactoryTalk View Studio SE, FactoryTalk Linx, SE Client / Runtime
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
01
STEP 01
Open FactoryTalk View Studio SE and load the training project for FactoryTalk View SE Manual.
v
02
STEP 02
Create or open the practical object for Add Numeric Display and Entry.
v
03
STEP 03
Configure the required tags, parameters, blocks or screen objects for this FactoryTalk View SE workflow.
v
04
STEP 04
Run compile, simulation, runtime or online monitoring as applicable and verify the practical behavior.
v
05
STEP 05
Save the work, record the result and tick Practical Add Numeric Display and Entry as complete.

Expected Result

Add Numeric Display and Entry is completed, verified and documented inside the FactoryTalk View SE Manual workflow.

P07

Softwell Digital Practical Manual

Practical 07 - Create Motor Control Display

Philosophy: Open the software, open the Softwell manual, and perform the practical.

FactoryTalk View SESCADAHMIAlarms
Software: FactoryTalk View Studio SE, FactoryTalk Linx, SE Client / Runtime
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
01
STEP 01
Open FactoryTalk View Studio SE and load the training project for FactoryTalk View SE Manual.
v
02
STEP 02
Create or open the practical object for Create Motor Control Display.
v
03
STEP 03
Configure the required tags, parameters, blocks or screen objects for this FactoryTalk View SE workflow.
v
04
STEP 04
Run compile, simulation, runtime or online monitoring as applicable and verify the practical behavior.
v
05
STEP 05
Save the work, record the result and tick Practical Create Motor Control Display as complete.

Expected Result

Create Motor Control Display is completed, verified and documented inside the FactoryTalk View SE Manual workflow.

P08

Softwell Digital Practical Manual

Practical 08 - Configure Global Objects

Philosophy: Open the software, open the Softwell manual, and perform the practical.

FactoryTalk View SESCADAHMIAlarms
Software: FactoryTalk View Studio SE, FactoryTalk Linx, SE Client / Runtime
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
01
STEP 01
Open FactoryTalk View Studio SE and load the training project for FactoryTalk View SE Manual.
v
02
STEP 02
Create or open the practical object for Configure Global Objects.
v
03
STEP 03
Configure the required tags, parameters, blocks or screen objects for this FactoryTalk View SE workflow.
v
04
STEP 04
Run compile, simulation, runtime or online monitoring as applicable and verify the practical behavior.
v
05
STEP 05
Save the work, record the result and tick Practical Configure Global Objects as complete.

Expected Result

Configure Global Objects is completed, verified and documented inside the FactoryTalk View SE Manual workflow.

P09

Softwell Digital Practical Manual

Practical 09 - Alarm and Event Setup

Philosophy: Open the software, open the Softwell manual, and perform the practical.

FactoryTalk View SESCADAHMIAlarms
Software: FactoryTalk View Studio SE, FactoryTalk Linx, SE Client / Runtime
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
01
STEP 01
Open FactoryTalk View Studio SE and load the training project for FactoryTalk View SE Manual.
v
02
STEP 02
Create or open the practical object for Alarm and Event Setup.
v
03
STEP 03
Configure the required tags, parameters, blocks or screen objects for this FactoryTalk View SE workflow.
v
04
STEP 04
Run compile, simulation, runtime or online monitoring as applicable and verify the practical behavior.
v
05
STEP 05
Save the work, record the result and tick Practical Alarm and Event Setup as complete.

Expected Result

Alarm and Event Setup is completed, verified and documented inside the FactoryTalk View SE Manual workflow.

P10

Softwell Digital Practical Manual

Practical 10 - Alarm Summary Display

Philosophy: Open the software, open the Softwell manual, and perform the practical.

FactoryTalk View SESCADAHMIAlarms
Software: FactoryTalk View Studio SE, FactoryTalk Linx, SE Client / Runtime
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
01
STEP 01
Open FactoryTalk View Studio SE and load the training project for FactoryTalk View SE Manual.
v
02
STEP 02
Create or open the practical object for Alarm Summary Display.
v
03
STEP 03
Configure the required tags, parameters, blocks or screen objects for this FactoryTalk View SE workflow.
v
04
STEP 04
Run compile, simulation, runtime or online monitoring as applicable and verify the practical behavior.
v
05
STEP 05
Save the work, record the result and tick Practical Alarm Summary Display as complete.

Expected Result

Alarm Summary Display is completed, verified and documented inside the FactoryTalk View SE Manual workflow.

P11

Softwell Digital Practical Manual

Practical 11 - Trend Display Practical

Philosophy: Open the software, open the Softwell manual, and perform the practical.

FactoryTalk View SESCADAHMIAlarms
Software: FactoryTalk View Studio SE, FactoryTalk Linx, SE Client / Runtime
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
01
STEP 01
Open FactoryTalk View Studio SE and load the training project for FactoryTalk View SE Manual.
v
02
STEP 02
Create or open the practical object for Trend Display Practical.
v
03
STEP 03
Configure the required tags, parameters, blocks or screen objects for this FactoryTalk View SE workflow.
v
04
STEP 04
Run compile, simulation, runtime or online monitoring as applicable and verify the practical behavior.
v
05
STEP 05
Save the work, record the result and tick Practical Trend Display Practical as complete.

Expected Result

Trend Display Practical is completed, verified and documented inside the FactoryTalk View SE Manual workflow.

P12

Softwell Digital Practical Manual

Practical 12 - Data Log Model Setup

Philosophy: Open the software, open the Softwell manual, and perform the practical.

FactoryTalk View SESCADAHMIAlarms
Software: FactoryTalk View Studio SE, FactoryTalk Linx, SE Client / Runtime
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
01
STEP 01
Open FactoryTalk View Studio SE and load the training project for FactoryTalk View SE Manual.
v
02
STEP 02
Create or open the practical object for Data Log Model Setup.
v
03
STEP 03
Configure the required tags, parameters, blocks or screen objects for this FactoryTalk View SE workflow.
v
04
STEP 04
Run compile, simulation, runtime or online monitoring as applicable and verify the practical behavior.
v
05
STEP 05
Save the work, record the result and tick Practical Data Log Model Setup as complete.

Expected Result

Data Log Model Setup is completed, verified and documented inside the FactoryTalk View SE Manual workflow.

P13

Softwell Digital Practical Manual

Practical 13 - User Security Setup

Philosophy: Open the software, open the Softwell manual, and perform the practical.

FactoryTalk View SESCADAHMIAlarms
Software: FactoryTalk View Studio SE, FactoryTalk Linx, SE Client / Runtime
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
01
STEP 01
Open FactoryTalk View Studio SE and load the training project for FactoryTalk View SE Manual.
v
02
STEP 02
Create or open the practical object for User Security Setup.
v
03
STEP 03
Configure the required tags, parameters, blocks or screen objects for this FactoryTalk View SE workflow.
v
04
STEP 04
Run compile, simulation, runtime or online monitoring as applicable and verify the practical behavior.
v
05
STEP 05
Save the work, record the result and tick Practical User Security Setup as complete.

Expected Result

User Security Setup is completed, verified and documented inside the FactoryTalk View SE Manual workflow.

P14

Softwell Digital Practical Manual

Practical 14 - Macro and Parameter File

Philosophy: Open the software, open the Softwell manual, and perform the practical.

FactoryTalk View SESCADAHMIAlarms
Software: FactoryTalk View Studio SE, FactoryTalk Linx, SE Client / Runtime
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
01
STEP 01
Open FactoryTalk View Studio SE and load the training project for FactoryTalk View SE Manual.
v
02
STEP 02
Create or open the practical object for Macro and Parameter File.
v
03
STEP 03
Configure the required tags, parameters, blocks or screen objects for this FactoryTalk View SE workflow.
v
04
STEP 04
Run compile, simulation, runtime or online monitoring as applicable and verify the practical behavior.
v
05
STEP 05
Save the work, record the result and tick Practical Macro and Parameter File as complete.

Expected Result

Macro and Parameter File is completed, verified and documented inside the FactoryTalk View SE Manual workflow.

P15

Softwell Digital Practical Manual

Practical 15 - SE Client Runtime Test

Philosophy: Open the software, open the Softwell manual, and perform the practical.

FactoryTalk View SESCADAHMIAlarms
Software: FactoryTalk View Studio SE, FactoryTalk Linx, SE Client / Runtime
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
01
STEP 01
Open FactoryTalk View Studio SE and load the training project for FactoryTalk View SE Manual.
v
02
STEP 02
Create or open the practical object for SE Client Runtime Test.
v
03
STEP 03
Configure the required tags, parameters, blocks or screen objects for this FactoryTalk View SE workflow.
v
04
STEP 04
Run compile, simulation, runtime or online monitoring as applicable and verify the practical behavior.
v
05
STEP 05
Save the work, record the result and tick Practical SE Client Runtime Test as complete.

Expected Result

SE Client Runtime Test is completed, verified and documented inside the FactoryTalk View SE Manual workflow.

P16

Softwell Digital Practical Manual

Practical 16 - Display Navigation Test

Philosophy: Open the software, open the Softwell manual, and perform the practical.

FactoryTalk View SESCADAHMIAlarms
Software: FactoryTalk View Studio SE, FactoryTalk Linx, SE Client / Runtime
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
01
STEP 01
Open FactoryTalk View Studio SE and load the training project for FactoryTalk View SE Manual.
v
02
STEP 02
Create or open the practical object for Display Navigation Test.
v
03
STEP 03
Configure the required tags, parameters, blocks or screen objects for this FactoryTalk View SE workflow.
v
04
STEP 04
Run compile, simulation, runtime or online monitoring as applicable and verify the practical behavior.
v
05
STEP 05
Save the work, record the result and tick Practical Display Navigation Test as complete.

Expected Result

Display Navigation Test is completed, verified and documented inside the FactoryTalk View SE Manual workflow.

P17

Softwell Digital Practical Manual

Practical 17 - Communication Diagnostics

Philosophy: Open the software, open the Softwell manual, and perform the practical.

FactoryTalk View SESCADAHMIAlarms
Software: FactoryTalk View Studio SE, FactoryTalk Linx, SE Client / Runtime
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
01
STEP 01
Open FactoryTalk View Studio SE and load the training project for FactoryTalk View SE Manual.
v
02
STEP 02
Create or open the practical object for Communication Diagnostics.
v
03
STEP 03
Configure the required tags, parameters, blocks or screen objects for this FactoryTalk View SE workflow.
v
04
STEP 04
Run compile, simulation, runtime or online monitoring as applicable and verify the practical behavior.
v
05
STEP 05
Save the work, record the result and tick Practical Communication Diagnostics as complete.

Expected Result

Communication Diagnostics is completed, verified and documented inside the FactoryTalk View SE Manual workflow.

P18

Softwell Digital Practical Manual

Practical 18 - Backup Application

Philosophy: Open the software, open the Softwell manual, and perform the practical.

FactoryTalk View SESCADAHMIAlarms
Software: FactoryTalk View Studio SE, FactoryTalk Linx, SE Client / Runtime
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
01
STEP 01
Open FactoryTalk View Studio SE and load the training project for FactoryTalk View SE Manual.
v
02
STEP 02
Create or open the practical object for Backup Application.
v
03
STEP 03
Configure the required tags, parameters, blocks or screen objects for this FactoryTalk View SE workflow.
v
04
STEP 04
Run compile, simulation, runtime or online monitoring as applicable and verify the practical behavior.
v
05
STEP 05
Save the work, record the result and tick Practical Backup Application as complete.

Expected Result

Backup Application is completed, verified and documented inside the FactoryTalk View SE Manual workflow.

P19

Softwell Digital Practical Manual

Practical 19 - Integrated SCADA Runtime Test

Philosophy: Open the software, open the Softwell manual, and perform the practical.

FactoryTalk View SESCADAHMIAlarms
Software: FactoryTalk View Studio SE, FactoryTalk Linx, SE Client / Runtime
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
01
STEP 01
Open FactoryTalk View Studio SE and load the training project for FactoryTalk View SE Manual.
v
02
STEP 02
Create or open the practical object for Integrated SCADA Runtime Test.
v
03
STEP 03
Configure the required tags, parameters, blocks or screen objects for this FactoryTalk View SE workflow.
v
04
STEP 04
Run compile, simulation, runtime or online monitoring as applicable and verify the practical behavior.
v
05
STEP 05
Save the work, record the result and tick Practical Integrated SCADA Runtime Test as complete.

Expected Result

Integrated SCADA Runtime Test is completed, verified and documented inside the FactoryTalk View SE Manual workflow.

P20

Softwell Digital Practical Manual

Practical 20 - Final FactoryTalk View SE Project

Philosophy: Open the software, open the Softwell manual, and perform the practical.

FactoryTalk View SESCADAHMIAlarms
Software: FactoryTalk View Studio SE, FactoryTalk Linx, SE Client / Runtime
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
01
STEP 01
Open FactoryTalk View Studio SE and load the training project for FactoryTalk View SE Manual.
v
02
STEP 02
Create or open the practical object for Final FactoryTalk View SE Project.
v
03
STEP 03
Configure the required tags, parameters, blocks or screen objects for this FactoryTalk View SE workflow.
v
04
STEP 04
Run compile, simulation, runtime or online monitoring as applicable and verify the practical behavior.
v
05
STEP 05
Save the work, record the result and tick Practical Final FactoryTalk View SE Project as complete.

Expected Result

Final FactoryTalk View SE Project is completed, verified and documented inside the FactoryTalk View SE Manual workflow.