Softwell Digital Practical Manual
Practical 01 - Create SE Application
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Create SE Application.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Create SE Application | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Create SE Application is completed, verified and documented inside the FactoryTalk View SE Manual workflow.
Talk to Automation Advisor
Get expert guidance for course selection, corporate training, project support and practical learning path.
Softwell Digital Practical Manual
Practical 02 - Set FactoryTalk Directory
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Set FactoryTalk Directory.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Set FactoryTalk Directory | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Set FactoryTalk Directory is completed, verified and documented inside the FactoryTalk View SE Manual workflow.
Skills & Tools You Will Learn
Important automation skills are arranged for job-level, project-level and Industry 4.0 learning.
Softwell Digital Practical Manual
Practical 03 - Add FactoryTalk Linx Shortcut
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Add FactoryTalk Linx Shortcut.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Add FactoryTalk Linx Shortcut | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Add FactoryTalk Linx Shortcut is completed, verified and documented inside the FactoryTalk View SE Manual workflow.
Softwell Digital Practical Manual
Practical 04 - Create HMI Tags
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Create HMI Tags.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Create HMI Tags | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Create HMI Tags is completed, verified and documented inside the FactoryTalk View SE Manual workflow.
Why Choose Softwell Automation
Learn automation with practical examples, industrial troubleshooting approach and complete IT/OT learning path.
Softwell Digital Practical Manual
Practical 05 - Create Main Graphic Display
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Create Main Graphic Display.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Create Main Graphic Display | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Create Main Graphic Display is completed, verified and documented inside the FactoryTalk View SE Manual workflow.
Course Contents / Curriculum
The curriculum follows a practical sequence from fundamentals to project integration.
Softwell Digital Practical Manual
Practical 06 - Add Numeric Display and Entry
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Add Numeric Display and Entry.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Add Numeric Display and Entry | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Add Numeric Display and Entry is completed, verified and documented inside the FactoryTalk View SE Manual workflow.
Frequently Asked Questions About FactoryTalk View SE Manual Site Edition SCADA Practical Manual
Who can join this training?
Students, freshers, working engineers, maintenance teams and corporate plant engineers can join based on their requirement.
Is practical training included?
Yes. The training is focused on PLC, SCADA, HMI, VFD, communication, troubleshooting and project based practice.
Can I request online or corporate training?
Yes. Softwell Automation provides classroom, online, corporate and in-plant training options.
Softwell Digital Practical Manual
Practical 07 - Create Motor Control Display
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Create Motor Control Display.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Create Motor Control Display | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Create Motor Control Display is completed, verified and documented inside the FactoryTalk View SE Manual workflow.
Softwell Digital Practical Manual
Practical 08 - Configure Global Objects
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Configure Global Objects.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Configure Global Objects | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Configure Global Objects is completed, verified and documented inside the FactoryTalk View SE Manual workflow.
Softwell Digital Practical Manual
Practical 09 - Alarm and Event Setup
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Alarm and Event Setup.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Alarm and Event Setup | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Alarm and Event Setup is completed, verified and documented inside the FactoryTalk View SE Manual workflow.
Softwell Digital Practical Manual
Practical 10 - Alarm Summary Display
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Alarm Summary Display.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Alarm Summary Display | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Alarm Summary Display is completed, verified and documented inside the FactoryTalk View SE Manual workflow.
Softwell Digital Practical Manual
Practical 11 - Trend Display Practical
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Trend Display Practical.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Trend Display Practical | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Trend Display Practical is completed, verified and documented inside the FactoryTalk View SE Manual workflow.
Softwell Digital Practical Manual
Practical 12 - Data Log Model Setup
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Data Log Model Setup.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Data Log Model Setup | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Data Log Model Setup is completed, verified and documented inside the FactoryTalk View SE Manual workflow.
Softwell Digital Practical Manual
Practical 13 - User Security Setup
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for User Security Setup.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | User Security Setup | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
User Security Setup is completed, verified and documented inside the FactoryTalk View SE Manual workflow.
Softwell Digital Practical Manual
Practical 14 - Macro and Parameter File
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Macro and Parameter File.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Macro and Parameter File | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Macro and Parameter File is completed, verified and documented inside the FactoryTalk View SE Manual workflow.
Softwell Digital Practical Manual
Practical 15 - SE Client Runtime Test
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for SE Client Runtime Test.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | SE Client Runtime Test | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
SE Client Runtime Test is completed, verified and documented inside the FactoryTalk View SE Manual workflow.
Softwell Digital Practical Manual
Practical 16 - Display Navigation Test
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Display Navigation Test.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Display Navigation Test | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Display Navigation Test is completed, verified and documented inside the FactoryTalk View SE Manual workflow.
Softwell Digital Practical Manual
Practical 17 - Communication Diagnostics
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Communication Diagnostics.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Communication Diagnostics | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Communication Diagnostics is completed, verified and documented inside the FactoryTalk View SE Manual workflow.
Softwell Digital Practical Manual
Practical 18 - Backup Application
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Backup Application.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Backup Application | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Backup Application is completed, verified and documented inside the FactoryTalk View SE Manual workflow.
Softwell Digital Practical Manual
Practical 19 - Integrated SCADA Runtime Test
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Integrated SCADA Runtime Test.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Integrated SCADA Runtime Test | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Integrated SCADA Runtime Test is completed, verified and documented inside the FactoryTalk View SE Manual workflow.
Softwell Digital Practical Manual
Practical 20 - Final FactoryTalk View SE Project
Philosophy: Open the software, open the Softwell manual, and perform the practical.
Setup: Engineering laptop, FactoryTalk application, Logix tags or simulator
A. Step-by-Step Procedure
B. Verification Checklist
- The project/configuration completes without an unresolved compile or device error.
- Online, simulation or runtime values respond in the expected sequence for Final FactoryTalk View SE Project.
- Critical addresses, parameters, units and initial states are checked against the lab sheet.
- The saved project can be reopened and the result reproduced without hidden manual correction.
C. If the Result Is Wrong
| Symptom | Probable cause | Diagnostic check | Corrective action |
|---|---|---|---|
| Compile or configuration error | Unresolved device, tag, type, address or parameter | Open the first diagnostic entry and trace it to the configured object | Correct the source item, compile again and save a new evidence record |
| No online/runtime response | Wrong connection, command source, permissions or scan state | Monitor live values from input through logic to output | Restore the verified connection/state and repeat one controlled test |
| Unstable or unexpected value | Scaling, initial state, timing or version mismatch | Compare raw and engineering values and review the installed version | Correct scaling/state, reset the lab safely and retest |
D. Student Evidence Record
Record software version, controller/device firmware, driver and license status.
Save the project/archive name, modified block/object and parameter list.
Capture a verified screenshot, trend, alarm, tag table or measured value.
Write the pass condition, fault tested, correction made and final observation.
| Practical | Final FactoryTalk View SE Project | Pass condition | Observed result matches the stated objective and can be repeated. |
|---|---|---|---|
| Evidence filename | ________________ | Trainer / self-check | ________________ |
Expected Result
Final FactoryTalk View SE Project is completed, verified and documented inside the FactoryTalk View SE Manual workflow.
Before You Start: Prerequisites, Tested Version, Safety and Evidence
This manual is a practical training workbook, not a substitute for the installed product manual or the site's approved engineering procedure. Record the exact software, firmware, license and hardware before following a step because menus and supported functions can vary by release.
Tested-version planning scope: Confirm FactoryTalk View SE Version 14 or the installed supported release, FactoryTalk Services, Linx and controller firmware compatibility. Enter the exact lab-tested software, firmware and hardware in the record below before course delivery; never assume cross-version compatibility.
Software build, firmware, device catalog, driver, communication interface and license status.
Use an isolated training system. Follow electrical, mechanical, process and cybersecurity controls before energizing or downloading.
Keep the source project, parameter/code export, screenshot/trend, fault test, correction and final pass result.
Last reviewed by Softwell Automation Technical Training Team on 17 July 2026.
| Field | Learner record | Verification |
|---|---|---|
| Software / firmware | ________________ | Matches the training device and official compatibility information |
| Project / backup | ________________ | Saved before and after the practical |
| Pass evidence | ________________ | Runtime value, trend, alarm, diagnostic or report attached |
| Fault tested | ________________ | Symptom, cause, check and corrective action documented |
Practice, Viva and Extension Challenge
Change one approved input or parameter, predict the result, execute the test and explain any difference.
Explain the data flow, safety boundary, first diagnostic check and recovery method without opening the answer.
Add one useful function while preserving the original pass criteria, alarm behavior and rollback path.
Combine at least three practicals, submit a versioned project and evidence pack, and demonstrate repeatable recovery.
Content status: Substantively reviewed and expanded 17 July 2026. Verify release-specific details against the linked official documentation.