SCL Programming Manual
Structured Control Language Practical Manual

Official Philosophy: Open the software, open the Softwell Notebook, and perform the practical.

20 Practical Steps
Action Flow Manual
No Theory / Only Practical
Softwell Training Template

Softwell
Digital Practical
Notebook

[check] Open -> Click -> Select -> Download -> Test -> Complete

NO THEORY * ONLY PRACTICAL
P01

Softwell Digital Practical Manual

Practical 01 - Create SCL Project

Philosophy: Open the software, open the Softwell manual, and perform the practical.

SCL ProgrammingPLC LogicFunctionsAutomation
Software: TIA Portal with SCL / Structured Control Language editor
Setup: Engineering laptop, PLC simulator or training PLC, sample I/O tags

A. Step-by-Step Procedure

01
STEP 01
Open TIA Portal and create a new training project.
v
02
STEP 02
Add a PLC CPU or simulator-supported controller.
v
03
STEP 03
Create a project folder named D:\Softwell_Training\SCL_Programming.
v
04
STEP 04
Save the project with the name Softwell_SCL_Manual.
v
05
STEP 05
Confirm the project tree is ready for program blocks.

B. Verification Checklist

  • The project/configuration completes without an unresolved compile or device error.
  • Online, simulation or runtime values respond in the expected sequence for Create SCL Project.
  • Critical addresses, parameters, units and initial states are checked against the lab sheet.
  • The saved project can be reopened and the result reproduced without hidden manual correction.

C. If the Result Is Wrong

SymptomProbable causeDiagnostic checkCorrective action
Compile or configuration errorUnresolved device, tag, type, address or parameterOpen the first diagnostic entry and trace it to the configured objectCorrect the source item, compile again and save a new evidence record
No online/runtime responseWrong connection, command source, permissions or scan stateMonitor live values from input through logic to outputRestore the verified connection/state and repeat one controlled test
Unstable or unexpected valueScaling, initial state, timing or version mismatchCompare raw and engineering values and review the installed versionCorrect scaling/state, reset the lab safely and retest

D. Student Evidence Record

Environment

Record software version, controller/device firmware, driver and license status.

Project evidence

Save the project/archive name, modified block/object and parameter list.

Runtime evidence

Capture a verified screenshot, trend, alarm, tag table or measured value.

Conclusion

Write the pass condition, fault tested, correction made and final observation.

VERIFIED SCREENSHOT / TREND / TAG-TABLE EVIDENCE
Insert a real capture from the learner's lab. Do not use a fabricated software screenshot.
PracticalCreate SCL ProjectPass conditionObserved result matches the stated objective and can be repeated.
Evidence filename________________Trainer / self-check________________

Expected Result

SCL training project is created and ready for programming blocks.

Talk to Automation Advisor

Get expert guidance for course selection, corporate training, project support and practical learning path.

Course GuidanceSelect the correct PLC SCADA, corporate, online or Industry 4.0 path.
Batch SupportGet schedule, duration, mode and prerequisite guidance.
Project AdviceDiscuss plant, automation, reporting or training requirement.
P02

Softwell Digital Practical Manual

Practical 02 - Create First SCL Function

Philosophy: Open the software, open the Softwell manual, and perform the practical.

SCL ProgrammingPLC LogicFunctionsAutomation
Software: TIA Portal with SCL / Structured Control Language editor
Setup: Engineering laptop, PLC simulator or training PLC, sample I/O tags

A. Step-by-Step Procedure

01
STEP 01
Open Program blocks and add a new Function.
v
02
STEP 02
Select language SCL and name it FC_First_SCL.
v
03
STEP 03
Create input variable StartCmd of type Bool.
v
04
STEP 04
Create output variable RunCmd of type Bool.
v
05
STEP 05
Write simple assignment RunCmd := StartCmd; and compile the block.

B. Verification Checklist

  • The project/configuration completes without an unresolved compile or device error.
  • Online, simulation or runtime values respond in the expected sequence for Create First SCL Function.
  • Critical addresses, parameters, units and initial states are checked against the lab sheet.
  • The saved project can be reopened and the result reproduced without hidden manual correction.

C. If the Result Is Wrong

SymptomProbable causeDiagnostic checkCorrective action
Compile or configuration errorUnresolved device, tag, type, address or parameterOpen the first diagnostic entry and trace it to the configured objectCorrect the source item, compile again and save a new evidence record
No online/runtime responseWrong connection, command source, permissions or scan stateMonitor live values from input through logic to outputRestore the verified connection/state and repeat one controlled test
Unstable or unexpected valueScaling, initial state, timing or version mismatchCompare raw and engineering values and review the installed versionCorrect scaling/state, reset the lab safely and retest

D. Student Evidence Record

Environment

Record software version, controller/device firmware, driver and license status.

Project evidence

Save the project/archive name, modified block/object and parameter list.

Runtime evidence

Capture a verified screenshot, trend, alarm, tag table or measured value.

Conclusion

Write the pass condition, fault tested, correction made and final observation.

VERIFIED SCREENSHOT / TREND / TAG-TABLE EVIDENCE
Insert a real capture from the learner's lab. Do not use a fabricated software screenshot.
PracticalCreate First SCL FunctionPass conditionObserved result matches the stated objective and can be repeated.
Evidence filename________________Trainer / self-check________________

Expected Result

First SCL function compiles successfully and copies input command to output command.

Skills & Tools You Will Learn

Important automation skills are arranged for job-level, project-level and Industry 4.0 learning.

PLC ProgrammingLadder, SCL/ST, hardware, I/O mapping and troubleshooting.
SCADA / HMITags, screens, alarms, trends, scripts and reporting.
Industry 4.0 ToolsOPC UA, SQL Server, Python, dashboards and Excel/PDF reports.
P03

Softwell Digital Practical Manual

Practical 03 - Call SCL Function from Main Program

Philosophy: Open the software, open the Softwell manual, and perform the practical.

SCL ProgrammingPLC LogicFunctionsAutomation
Software: TIA Portal with SCL / Structured Control Language editor
Setup: Engineering laptop, PLC simulator or training PLC, sample I/O tags

A. Step-by-Step Procedure

01
STEP 01
Open the main program block.
v
02
STEP 02
Drag or call FC_First_SCL inside the main logic.
v
03
STEP 03
Connect StartCmd to a test tag or memory bit.
v
04
STEP 04
Connect RunCmd to an output or memory bit.
v
05
STEP 05
Compile and monitor the logic online or in simulation.

B. Verification Checklist

  • The project/configuration completes without an unresolved compile or device error.
  • Online, simulation or runtime values respond in the expected sequence for Call SCL Function from Main Program.
  • Critical addresses, parameters, units and initial states are checked against the lab sheet.
  • The saved project can be reopened and the result reproduced without hidden manual correction.

C. If the Result Is Wrong

SymptomProbable causeDiagnostic checkCorrective action
Compile or configuration errorUnresolved device, tag, type, address or parameterOpen the first diagnostic entry and trace it to the configured objectCorrect the source item, compile again and save a new evidence record
No online/runtime responseWrong connection, command source, permissions or scan stateMonitor live values from input through logic to outputRestore the verified connection/state and repeat one controlled test
Unstable or unexpected valueScaling, initial state, timing or version mismatchCompare raw and engineering values and review the installed versionCorrect scaling/state, reset the lab safely and retest

D. Student Evidence Record

Environment

Record software version, controller/device firmware, driver and license status.

Project evidence

Save the project/archive name, modified block/object and parameter list.

Runtime evidence

Capture a verified screenshot, trend, alarm, tag table or measured value.

Conclusion

Write the pass condition, fault tested, correction made and final observation.

VERIFIED SCREENSHOT / TREND / TAG-TABLE EVIDENCE
Insert a real capture from the learner's lab. Do not use a fabricated software screenshot.
PracticalCall SCL Function from Main ProgramPass conditionObserved result matches the stated objective and can be repeated.
Evidence filename________________Trainer / self-check________________

Expected Result

SCL function is called from the main program and responds to the test input.

P04

Softwell Digital Practical Manual

Practical 04 - Boolean Logic in SCL

Philosophy: Open the software, open the Softwell manual, and perform the practical.

SCL ProgrammingPLC LogicFunctionsAutomation
Software: TIA Portal with SCL / Structured Control Language editor
Setup: Engineering laptop, PLC simulator or training PLC, sample I/O tags

A. Step-by-Step Procedure

01
STEP 01
Create FC_Boolean_Logic in SCL.
v
02
STEP 02
Add inputs StartPB, StopPB and FaultActive.
v
03
STEP 03
Add output MotorRun.
v
04
STEP 04
Write logic using AND, OR and NOT operators.
v
05
STEP 05
Test all input combinations using watch table or simulation.

B. Verification Checklist

  • The project/configuration completes without an unresolved compile or device error.
  • Online, simulation or runtime values respond in the expected sequence for Boolean Logic in SCL.
  • Critical addresses, parameters, units and initial states are checked against the lab sheet.
  • The saved project can be reopened and the result reproduced without hidden manual correction.

C. If the Result Is Wrong

SymptomProbable causeDiagnostic checkCorrective action
Compile or configuration errorUnresolved device, tag, type, address or parameterOpen the first diagnostic entry and trace it to the configured objectCorrect the source item, compile again and save a new evidence record
No online/runtime responseWrong connection, command source, permissions or scan stateMonitor live values from input through logic to outputRestore the verified connection/state and repeat one controlled test
Unstable or unexpected valueScaling, initial state, timing or version mismatchCompare raw and engineering values and review the installed versionCorrect scaling/state, reset the lab safely and retest

D. Student Evidence Record

Environment

Record software version, controller/device firmware, driver and license status.

Project evidence

Save the project/archive name, modified block/object and parameter list.

Runtime evidence

Capture a verified screenshot, trend, alarm, tag table or measured value.

Conclusion

Write the pass condition, fault tested, correction made and final observation.

VERIFIED SCREENSHOT / TREND / TAG-TABLE EVIDENCE
Insert a real capture from the learner's lab. Do not use a fabricated software screenshot.
PracticalBoolean Logic in SCLPass conditionObserved result matches the stated objective and can be repeated.
Evidence filename________________Trainer / self-check________________

Expected Result

Boolean SCL logic correctly controls MotorRun based on start, stop and fault status.

Why Choose Softwell Automation

Learn automation with practical examples, industrial troubleshooting approach and complete IT/OT learning path.

Industry Experienced TrainerReal plant examples and project based training.
Hands-on LearningPLC logic, SCADA, VFD, communication and reporting practice.
Flexible ModesOnline, classroom, corporate and in-plant options.
P05

Softwell Digital Practical Manual

Practical 05 - Set Reset Logic

Philosophy: Open the software, open the Softwell manual, and perform the practical.

SCL ProgrammingPLC LogicFunctionsAutomation
Software: TIA Portal with SCL / Structured Control Language editor
Setup: Engineering laptop, PLC simulator or training PLC, sample I/O tags

A. Step-by-Step Procedure

01
STEP 01
Create a function block FB_Motor_Latch in SCL.
v
02
STEP 02
Add StartPB, StopPB and Fault inputs.
v
03
STEP 03
Add static variable RunMemory.
v
04
STEP 04
Write latch logic so Start sets and Stop/Fault resets RunMemory.
v
05
STEP 05
Compile, call the FB with an instance DB and test.

B. Verification Checklist

  • The project/configuration completes without an unresolved compile or device error.
  • Online, simulation or runtime values respond in the expected sequence for Set Reset Logic.
  • Critical addresses, parameters, units and initial states are checked against the lab sheet.
  • The saved project can be reopened and the result reproduced without hidden manual correction.

C. If the Result Is Wrong

SymptomProbable causeDiagnostic checkCorrective action
Compile or configuration errorUnresolved device, tag, type, address or parameterOpen the first diagnostic entry and trace it to the configured objectCorrect the source item, compile again and save a new evidence record
No online/runtime responseWrong connection, command source, permissions or scan stateMonitor live values from input through logic to outputRestore the verified connection/state and repeat one controlled test
Unstable or unexpected valueScaling, initial state, timing or version mismatchCompare raw and engineering values and review the installed versionCorrect scaling/state, reset the lab safely and retest

D. Student Evidence Record

Environment

Record software version, controller/device firmware, driver and license status.

Project evidence

Save the project/archive name, modified block/object and parameter list.

Runtime evidence

Capture a verified screenshot, trend, alarm, tag table or measured value.

Conclusion

Write the pass condition, fault tested, correction made and final observation.

VERIFIED SCREENSHOT / TREND / TAG-TABLE EVIDENCE
Insert a real capture from the learner's lab. Do not use a fabricated software screenshot.
PracticalSet Reset LogicPass conditionObserved result matches the stated objective and can be repeated.
Evidence filename________________Trainer / self-check________________

Expected Result

Motor latch keeps run command active until stop or fault condition resets it.

Course Contents / Curriculum

The curriculum follows a practical sequence from fundamentals to project integration.

Level 01Basic PLC, wiring, addressing and ladder logic.
Level 02Advanced PLC, networking, SCADA and diagnostics.
Level 03OPC UA, SQL, Python, reports and IT/OT integration.
P06

Softwell Digital Practical Manual

Practical 06 - Timer Logic in SCL

Philosophy: Open the software, open the Softwell manual, and perform the practical.

SCL ProgrammingPLC LogicFunctionsAutomation
Software: TIA Portal with SCL / Structured Control Language editor
Setup: Engineering laptop, PLC simulator or training PLC, sample I/O tags

A. Step-by-Step Procedure

01
STEP 01
Create FB_StartDelay in SCL.
v
02
STEP 02
Declare TON timer instance in the static area.
v
03
STEP 03
Add StartCmd input and DelayedRun output.
v
04
STEP 04
Call the TON timer with PT value T#5s.
v
05
STEP 05
Test that DelayedRun turns ON after the delay time.

B. Verification Checklist

  • The project/configuration completes without an unresolved compile or device error.
  • Online, simulation or runtime values respond in the expected sequence for Timer Logic in SCL.
  • Critical addresses, parameters, units and initial states are checked against the lab sheet.
  • The saved project can be reopened and the result reproduced without hidden manual correction.

C. If the Result Is Wrong

SymptomProbable causeDiagnostic checkCorrective action
Compile or configuration errorUnresolved device, tag, type, address or parameterOpen the first diagnostic entry and trace it to the configured objectCorrect the source item, compile again and save a new evidence record
No online/runtime responseWrong connection, command source, permissions or scan stateMonitor live values from input through logic to outputRestore the verified connection/state and repeat one controlled test
Unstable or unexpected valueScaling, initial state, timing or version mismatchCompare raw and engineering values and review the installed versionCorrect scaling/state, reset the lab safely and retest

D. Student Evidence Record

Environment

Record software version, controller/device firmware, driver and license status.

Project evidence

Save the project/archive name, modified block/object and parameter list.

Runtime evidence

Capture a verified screenshot, trend, alarm, tag table or measured value.

Conclusion

Write the pass condition, fault tested, correction made and final observation.

VERIFIED SCREENSHOT / TREND / TAG-TABLE EVIDENCE
Insert a real capture from the learner's lab. Do not use a fabricated software screenshot.
PracticalTimer Logic in SCLPass conditionObserved result matches the stated objective and can be repeated.
Evidence filename________________Trainer / self-check________________

Expected Result

SCL timer logic creates a verified start delay.

Frequently Asked Questions About SCL Programming Manual Structured Control Language Practical Manual

Who can join this training?

Students, freshers, working engineers, maintenance teams and corporate plant engineers can join based on their requirement.

Is practical training included?

Yes. The training is focused on PLC, SCADA, HMI, VFD, communication, troubleshooting and project based practice.

Can I request online or corporate training?

Yes. Softwell Automation provides classroom, online, corporate and in-plant training options.

P07

Softwell Digital Practical Manual

Practical 07 - Counter Logic in SCL

Philosophy: Open the software, open the Softwell manual, and perform the practical.

SCL ProgrammingPLC LogicFunctionsAutomation
Software: TIA Portal with SCL / Structured Control Language editor
Setup: Engineering laptop, PLC simulator or training PLC, sample I/O tags

A. Step-by-Step Procedure

01
STEP 01
Create FB_PartCounter in SCL.
v
02
STEP 02
Add PartSensor input and Reset input.
v
03
STEP 03
Use rising edge logic or counter instruction as per trainer setup.
v
04
STEP 04
Increment CountValue for every detected part.
v
05
STEP 05
Reset CountValue when Reset is true.

B. Verification Checklist

  • The project/configuration completes without an unresolved compile or device error.
  • Online, simulation or runtime values respond in the expected sequence for Counter Logic in SCL.
  • Critical addresses, parameters, units and initial states are checked against the lab sheet.
  • The saved project can be reopened and the result reproduced without hidden manual correction.

C. If the Result Is Wrong

SymptomProbable causeDiagnostic checkCorrective action
Compile or configuration errorUnresolved device, tag, type, address or parameterOpen the first diagnostic entry and trace it to the configured objectCorrect the source item, compile again and save a new evidence record
No online/runtime responseWrong connection, command source, permissions or scan stateMonitor live values from input through logic to outputRestore the verified connection/state and repeat one controlled test
Unstable or unexpected valueScaling, initial state, timing or version mismatchCompare raw and engineering values and review the installed versionCorrect scaling/state, reset the lab safely and retest

D. Student Evidence Record

Environment

Record software version, controller/device firmware, driver and license status.

Project evidence

Save the project/archive name, modified block/object and parameter list.

Runtime evidence

Capture a verified screenshot, trend, alarm, tag table or measured value.

Conclusion

Write the pass condition, fault tested, correction made and final observation.

VERIFIED SCREENSHOT / TREND / TAG-TABLE EVIDENCE
Insert a real capture from the learner's lab. Do not use a fabricated software screenshot.
PracticalCounter Logic in SCLPass conditionObserved result matches the stated objective and can be repeated.
Evidence filename________________Trainer / self-check________________

Expected Result

Part counter increments on sensor pulses and resets correctly.

P08

Softwell Digital Practical Manual

Practical 08 - Analog Scaling Function

Philosophy: Open the software, open the Softwell manual, and perform the practical.

SCL ProgrammingPLC LogicFunctionsAutomation
Software: TIA Portal with SCL / Structured Control Language editor
Setup: Engineering laptop, PLC simulator or training PLC, sample I/O tags

A. Step-by-Step Procedure

01
STEP 01
Create FC_Scale_Analog in SCL.
v
02
STEP 02
Add RawValue, RawMin, RawMax, EngMin and EngMax inputs.
v
03
STEP 03
Add ScaledValue output as Real.
v
04
STEP 04
Write linear scaling formula in SCL.
v
05
STEP 05
Test using raw values 0, 13824 and 27648.

B. Verification Checklist

  • The project/configuration completes without an unresolved compile or device error.
  • Online, simulation or runtime values respond in the expected sequence for Analog Scaling Function.
  • Critical addresses, parameters, units and initial states are checked against the lab sheet.
  • The saved project can be reopened and the result reproduced without hidden manual correction.

C. If the Result Is Wrong

SymptomProbable causeDiagnostic checkCorrective action
Compile or configuration errorUnresolved device, tag, type, address or parameterOpen the first diagnostic entry and trace it to the configured objectCorrect the source item, compile again and save a new evidence record
No online/runtime responseWrong connection, command source, permissions or scan stateMonitor live values from input through logic to outputRestore the verified connection/state and repeat one controlled test
Unstable or unexpected valueScaling, initial state, timing or version mismatchCompare raw and engineering values and review the installed versionCorrect scaling/state, reset the lab safely and retest

D. Student Evidence Record

Environment

Record software version, controller/device firmware, driver and license status.

Project evidence

Save the project/archive name, modified block/object and parameter list.

Runtime evidence

Capture a verified screenshot, trend, alarm, tag table or measured value.

Conclusion

Write the pass condition, fault tested, correction made and final observation.

VERIFIED SCREENSHOT / TREND / TAG-TABLE EVIDENCE
Insert a real capture from the learner's lab. Do not use a fabricated software screenshot.
PracticalAnalog Scaling FunctionPass conditionObserved result matches the stated objective and can be repeated.
Evidence filename________________Trainer / self-check________________

Expected Result

Analog raw value is converted into engineering units using SCL formula.

P09

Softwell Digital Practical Manual

Practical 09 - Limit and Alarm Logic

Philosophy: Open the software, open the Softwell manual, and perform the practical.

SCL ProgrammingPLC LogicFunctionsAutomation
Software: TIA Portal with SCL / Structured Control Language editor
Setup: Engineering laptop, PLC simulator or training PLC, sample I/O tags

A. Step-by-Step Procedure

01
STEP 01
Create FC_Limit_Check in SCL.
v
02
STEP 02
Add ProcessValue, LowLimit and HighLimit inputs.
v
03
STEP 03
Add LowAlarm, HighAlarm and Normal outputs.
v
04
STEP 04
Write comparison logic using less-than and greater-than operators.
v
05
STEP 05
Test below, within and above limit values.

B. Verification Checklist

  • The project/configuration completes without an unresolved compile or device error.
  • Online, simulation or runtime values respond in the expected sequence for Limit and Alarm Logic.
  • Critical addresses, parameters, units and initial states are checked against the lab sheet.
  • The saved project can be reopened and the result reproduced without hidden manual correction.

C. If the Result Is Wrong

SymptomProbable causeDiagnostic checkCorrective action
Compile or configuration errorUnresolved device, tag, type, address or parameterOpen the first diagnostic entry and trace it to the configured objectCorrect the source item, compile again and save a new evidence record
No online/runtime responseWrong connection, command source, permissions or scan stateMonitor live values from input through logic to outputRestore the verified connection/state and repeat one controlled test
Unstable or unexpected valueScaling, initial state, timing or version mismatchCompare raw and engineering values and review the installed versionCorrect scaling/state, reset the lab safely and retest

D. Student Evidence Record

Environment

Record software version, controller/device firmware, driver and license status.

Project evidence

Save the project/archive name, modified block/object and parameter list.

Runtime evidence

Capture a verified screenshot, trend, alarm, tag table or measured value.

Conclusion

Write the pass condition, fault tested, correction made and final observation.

VERIFIED SCREENSHOT / TREND / TAG-TABLE EVIDENCE
Insert a real capture from the learner's lab. Do not use a fabricated software screenshot.
PracticalLimit and Alarm LogicPass conditionObserved result matches the stated objective and can be repeated.
Evidence filename________________Trainer / self-check________________

Expected Result

SCL comparison logic generates low, high and normal status outputs correctly.

P10

Softwell Digital Practical Manual

Practical 10 - Case Statement Practical

Philosophy: Open the software, open the Softwell manual, and perform the practical.

SCL ProgrammingPLC LogicFunctionsAutomation
Software: TIA Portal with SCL / Structured Control Language editor
Setup: Engineering laptop, PLC simulator or training PLC, sample I/O tags

A. Step-by-Step Procedure

01
STEP 01
Create FC_Mode_Select in SCL.
v
02
STEP 02
Add ModeNo input as Int.
v
03
STEP 03
Add AutoMode, ManualMode and MaintenanceMode outputs.
v
04
STEP 04
Use CASE ModeNo OF for mode selection.
v
05
STEP 05
Test ModeNo values 1, 2, 3 and invalid value.

B. Verification Checklist

  • The project/configuration completes without an unresolved compile or device error.
  • Online, simulation or runtime values respond in the expected sequence for Case Statement Practical.
  • Critical addresses, parameters, units and initial states are checked against the lab sheet.
  • The saved project can be reopened and the result reproduced without hidden manual correction.

C. If the Result Is Wrong

SymptomProbable causeDiagnostic checkCorrective action
Compile or configuration errorUnresolved device, tag, type, address or parameterOpen the first diagnostic entry and trace it to the configured objectCorrect the source item, compile again and save a new evidence record
No online/runtime responseWrong connection, command source, permissions or scan stateMonitor live values from input through logic to outputRestore the verified connection/state and repeat one controlled test
Unstable or unexpected valueScaling, initial state, timing or version mismatchCompare raw and engineering values and review the installed versionCorrect scaling/state, reset the lab safely and retest

D. Student Evidence Record

Environment

Record software version, controller/device firmware, driver and license status.

Project evidence

Save the project/archive name, modified block/object and parameter list.

Runtime evidence

Capture a verified screenshot, trend, alarm, tag table or measured value.

Conclusion

Write the pass condition, fault tested, correction made and final observation.

VERIFIED SCREENSHOT / TREND / TAG-TABLE EVIDENCE
Insert a real capture from the learner's lab. Do not use a fabricated software screenshot.
PracticalCase Statement PracticalPass conditionObserved result matches the stated objective and can be repeated.
Evidence filename________________Trainer / self-check________________

Expected Result

CASE statement selects the correct operating mode and handles invalid mode values.

P11

Softwell Digital Practical Manual

Practical 11 - For Loop Practical

Philosophy: Open the software, open the Softwell manual, and perform the practical.

SCL ProgrammingPLC LogicFunctionsAutomation
Software: TIA Portal with SCL / Structured Control Language editor
Setup: Engineering laptop, PLC simulator or training PLC, sample I/O tags

A. Step-by-Step Procedure

01
STEP 01
Create FC_Array_Total in SCL.
v
02
STEP 02
Create an array input or internal array of production counts.
v
03
STEP 03
Use FOR loop to add all array values.
v
04
STEP 04
Store result in TotalCount output.
v
05
STEP 05
Test with known sample values and compare manually.

B. Verification Checklist

  • The project/configuration completes without an unresolved compile or device error.
  • Online, simulation or runtime values respond in the expected sequence for For Loop Practical.
  • Critical addresses, parameters, units and initial states are checked against the lab sheet.
  • The saved project can be reopened and the result reproduced without hidden manual correction.

C. If the Result Is Wrong

SymptomProbable causeDiagnostic checkCorrective action
Compile or configuration errorUnresolved device, tag, type, address or parameterOpen the first diagnostic entry and trace it to the configured objectCorrect the source item, compile again and save a new evidence record
No online/runtime responseWrong connection, command source, permissions or scan stateMonitor live values from input through logic to outputRestore the verified connection/state and repeat one controlled test
Unstable or unexpected valueScaling, initial state, timing or version mismatchCompare raw and engineering values and review the installed versionCorrect scaling/state, reset the lab safely and retest

D. Student Evidence Record

Environment

Record software version, controller/device firmware, driver and license status.

Project evidence

Save the project/archive name, modified block/object and parameter list.

Runtime evidence

Capture a verified screenshot, trend, alarm, tag table or measured value.

Conclusion

Write the pass condition, fault tested, correction made and final observation.

VERIFIED SCREENSHOT / TREND / TAG-TABLE EVIDENCE
Insert a real capture from the learner's lab. Do not use a fabricated software screenshot.
PracticalFor Loop PracticalPass conditionObserved result matches the stated objective and can be repeated.
Evidence filename________________Trainer / self-check________________

Expected Result

FOR loop calculates total count from array values.

P12

Softwell Digital Practical Manual

Practical 12 - Array Average Function

Philosophy: Open the software, open the Softwell manual, and perform the practical.

SCL ProgrammingPLC LogicFunctionsAutomation
Software: TIA Portal with SCL / Structured Control Language editor
Setup: Engineering laptop, PLC simulator or training PLC, sample I/O tags

A. Step-by-Step Procedure

01
STEP 01
Create FC_Array_Average in SCL.
v
02
STEP 02
Use an array of Real values as sample data.
v
03
STEP 03
Loop through all values and calculate sum.
v
04
STEP 04
Divide by number of samples to create AverageValue.
v
05
STEP 05
Test the function with simple known values.

B. Verification Checklist

  • The project/configuration completes without an unresolved compile or device error.
  • Online, simulation or runtime values respond in the expected sequence for Array Average Function.
  • Critical addresses, parameters, units and initial states are checked against the lab sheet.
  • The saved project can be reopened and the result reproduced without hidden manual correction.

C. If the Result Is Wrong

SymptomProbable causeDiagnostic checkCorrective action
Compile or configuration errorUnresolved device, tag, type, address or parameterOpen the first diagnostic entry and trace it to the configured objectCorrect the source item, compile again and save a new evidence record
No online/runtime responseWrong connection, command source, permissions or scan stateMonitor live values from input through logic to outputRestore the verified connection/state and repeat one controlled test
Unstable or unexpected valueScaling, initial state, timing or version mismatchCompare raw and engineering values and review the installed versionCorrect scaling/state, reset the lab safely and retest

D. Student Evidence Record

Environment

Record software version, controller/device firmware, driver and license status.

Project evidence

Save the project/archive name, modified block/object and parameter list.

Runtime evidence

Capture a verified screenshot, trend, alarm, tag table or measured value.

Conclusion

Write the pass condition, fault tested, correction made and final observation.

VERIFIED SCREENSHOT / TREND / TAG-TABLE EVIDENCE
Insert a real capture from the learner's lab. Do not use a fabricated software screenshot.
PracticalArray Average FunctionPass conditionObserved result matches the stated objective and can be repeated.
Evidence filename________________Trainer / self-check________________

Expected Result

SCL array average calculation returns the expected average value.

P13

Softwell Digital Practical Manual

Practical 13 - String Handling in SCL

Philosophy: Open the software, open the Softwell manual, and perform the practical.

SCL ProgrammingPLC LogicFunctionsAutomation
Software: TIA Portal with SCL / Structured Control Language editor
Setup: Engineering laptop, PLC simulator or training PLC, sample I/O tags

A. Step-by-Step Procedure

01
STEP 01
Create FC_Batch_String in SCL.
v
02
STEP 02
Add BatchPrefix and BatchNumber inputs.
v
03
STEP 03
Convert or combine values into a batch text string as per available functions.
v
04
STEP 04
Store final text in BatchName output.
v
05
STEP 05
Monitor output for different batch numbers.

B. Verification Checklist

  • The project/configuration completes without an unresolved compile or device error.
  • Online, simulation or runtime values respond in the expected sequence for String Handling in SCL.
  • Critical addresses, parameters, units and initial states are checked against the lab sheet.
  • The saved project can be reopened and the result reproduced without hidden manual correction.

C. If the Result Is Wrong

SymptomProbable causeDiagnostic checkCorrective action
Compile or configuration errorUnresolved device, tag, type, address or parameterOpen the first diagnostic entry and trace it to the configured objectCorrect the source item, compile again and save a new evidence record
No online/runtime responseWrong connection, command source, permissions or scan stateMonitor live values from input through logic to outputRestore the verified connection/state and repeat one controlled test
Unstable or unexpected valueScaling, initial state, timing or version mismatchCompare raw and engineering values and review the installed versionCorrect scaling/state, reset the lab safely and retest

D. Student Evidence Record

Environment

Record software version, controller/device firmware, driver and license status.

Project evidence

Save the project/archive name, modified block/object and parameter list.

Runtime evidence

Capture a verified screenshot, trend, alarm, tag table or measured value.

Conclusion

Write the pass condition, fault tested, correction made and final observation.

VERIFIED SCREENSHOT / TREND / TAG-TABLE EVIDENCE
Insert a real capture from the learner's lab. Do not use a fabricated software screenshot.
PracticalString Handling in SCLPass conditionObserved result matches the stated objective and can be repeated.
Evidence filename________________Trainer / self-check________________

Expected Result

SCL string logic creates a readable batch name for reports and HMI display.

P14

Softwell Digital Practical Manual

Practical 14 - Function Block with Instance DB

Philosophy: Open the software, open the Softwell manual, and perform the practical.

SCL ProgrammingPLC LogicFunctionsAutomation
Software: TIA Portal with SCL / Structured Control Language editor
Setup: Engineering laptop, PLC simulator or training PLC, sample I/O tags

A. Step-by-Step Procedure

01
STEP 01
Create FB_Valve_Control in SCL.
v
02
STEP 02
Add OpenCmd, CloseCmd, OpenFB and CloseFB signals.
v
03
STEP 03
Use static variables for internal command memory and fault status.
v
04
STEP 04
Call FB_Valve_Control twice with separate instance DBs.
v
05
STEP 05
Verify both valve instances work independently.

B. Verification Checklist

  • The project/configuration completes without an unresolved compile or device error.
  • Online, simulation or runtime values respond in the expected sequence for Function Block with Instance DB.
  • Critical addresses, parameters, units and initial states are checked against the lab sheet.
  • The saved project can be reopened and the result reproduced without hidden manual correction.

C. If the Result Is Wrong

SymptomProbable causeDiagnostic checkCorrective action
Compile or configuration errorUnresolved device, tag, type, address or parameterOpen the first diagnostic entry and trace it to the configured objectCorrect the source item, compile again and save a new evidence record
No online/runtime responseWrong connection, command source, permissions or scan stateMonitor live values from input through logic to outputRestore the verified connection/state and repeat one controlled test
Unstable or unexpected valueScaling, initial state, timing or version mismatchCompare raw and engineering values and review the installed versionCorrect scaling/state, reset the lab safely and retest

D. Student Evidence Record

Environment

Record software version, controller/device firmware, driver and license status.

Project evidence

Save the project/archive name, modified block/object and parameter list.

Runtime evidence

Capture a verified screenshot, trend, alarm, tag table or measured value.

Conclusion

Write the pass condition, fault tested, correction made and final observation.

VERIFIED SCREENSHOT / TREND / TAG-TABLE EVIDENCE
Insert a real capture from the learner's lab. Do not use a fabricated software screenshot.
PracticalFunction Block with Instance DBPass conditionObserved result matches the stated objective and can be repeated.
Evidence filename________________Trainer / self-check________________

Expected Result

Reusable SCL function block controls multiple valves with separate instance data.

P15

Softwell Digital Practical Manual

Practical 15 - Data Block Access

Philosophy: Open the software, open the Softwell manual, and perform the practical.

SCL ProgrammingPLC LogicFunctionsAutomation
Software: TIA Portal with SCL / Structured Control Language editor
Setup: Engineering laptop, PLC simulator or training PLC, sample I/O tags

A. Step-by-Step Procedure

01
STEP 01
Create a global data block DB_Process_Setpoints.
v
02
STEP 02
Add setpoints for speed, temperature and pressure.
v
03
STEP 03
Read these setpoints inside an SCL block.
v
04
STEP 04
Use the values in limit or scaling calculations.
v
05
STEP 05
Modify DB values online and verify SCL logic updates.

B. Verification Checklist

  • The project/configuration completes without an unresolved compile or device error.
  • Online, simulation or runtime values respond in the expected sequence for Data Block Access.
  • Critical addresses, parameters, units and initial states are checked against the lab sheet.
  • The saved project can be reopened and the result reproduced without hidden manual correction.

C. If the Result Is Wrong

SymptomProbable causeDiagnostic checkCorrective action
Compile or configuration errorUnresolved device, tag, type, address or parameterOpen the first diagnostic entry and trace it to the configured objectCorrect the source item, compile again and save a new evidence record
No online/runtime responseWrong connection, command source, permissions or scan stateMonitor live values from input through logic to outputRestore the verified connection/state and repeat one controlled test
Unstable or unexpected valueScaling, initial state, timing or version mismatchCompare raw and engineering values and review the installed versionCorrect scaling/state, reset the lab safely and retest

D. Student Evidence Record

Environment

Record software version, controller/device firmware, driver and license status.

Project evidence

Save the project/archive name, modified block/object and parameter list.

Runtime evidence

Capture a verified screenshot, trend, alarm, tag table or measured value.

Conclusion

Write the pass condition, fault tested, correction made and final observation.

VERIFIED SCREENSHOT / TREND / TAG-TABLE EVIDENCE
Insert a real capture from the learner's lab. Do not use a fabricated software screenshot.
PracticalData Block AccessPass conditionObserved result matches the stated objective and can be repeated.
Evidence filename________________Trainer / self-check________________

Expected Result

SCL block reads and uses global data block setpoints.

P16

Softwell Digital Practical Manual

Practical 16 - Fault Code Generation

Philosophy: Open the software, open the Softwell manual, and perform the practical.

SCL ProgrammingPLC LogicFunctionsAutomation
Software: TIA Portal with SCL / Structured Control Language editor
Setup: Engineering laptop, PLC simulator or training PLC, sample I/O tags

A. Step-by-Step Procedure

01
STEP 01
Create FC_Fault_Code in SCL.
v
02
STEP 02
Add multiple alarm inputs such as EStop, Overload and HighTemp.
v
03
STEP 03
Assign numeric fault codes based on priority.
v
04
STEP 04
Use IF ELSIF structure for priority handling.
v
05
STEP 05
Test that highest priority fault code is selected.

B. Verification Checklist

  • The project/configuration completes without an unresolved compile or device error.
  • Online, simulation or runtime values respond in the expected sequence for Fault Code Generation.
  • Critical addresses, parameters, units and initial states are checked against the lab sheet.
  • The saved project can be reopened and the result reproduced without hidden manual correction.

C. If the Result Is Wrong

SymptomProbable causeDiagnostic checkCorrective action
Compile or configuration errorUnresolved device, tag, type, address or parameterOpen the first diagnostic entry and trace it to the configured objectCorrect the source item, compile again and save a new evidence record
No online/runtime responseWrong connection, command source, permissions or scan stateMonitor live values from input through logic to outputRestore the verified connection/state and repeat one controlled test
Unstable or unexpected valueScaling, initial state, timing or version mismatchCompare raw and engineering values and review the installed versionCorrect scaling/state, reset the lab safely and retest

D. Student Evidence Record

Environment

Record software version, controller/device firmware, driver and license status.

Project evidence

Save the project/archive name, modified block/object and parameter list.

Runtime evidence

Capture a verified screenshot, trend, alarm, tag table or measured value.

Conclusion

Write the pass condition, fault tested, correction made and final observation.

VERIFIED SCREENSHOT / TREND / TAG-TABLE EVIDENCE
Insert a real capture from the learner's lab. Do not use a fabricated software screenshot.
PracticalFault Code GenerationPass conditionObserved result matches the stated objective and can be repeated.
Evidence filename________________Trainer / self-check________________

Expected Result

SCL fault code logic produces correct priority-based diagnostic code.

P17

Softwell Digital Practical Manual

Practical 17 - Machine Sequence in SCL

Philosophy: Open the software, open the Softwell manual, and perform the practical.

SCL ProgrammingPLC LogicFunctionsAutomation
Software: TIA Portal with SCL / Structured Control Language editor
Setup: Engineering laptop, PLC simulator or training PLC, sample I/O tags

A. Step-by-Step Procedure

01
STEP 01
Create FB_Sequence_Control in SCL.
v
02
STEP 02
Declare StepNo as static integer.
v
03
STEP 03
Use CASE StepNo OF to build sequence steps.
v
04
STEP 04
Add transition conditions for Start, SensorDone and Reset.
v
05
STEP 05
Monitor StepNo while running simulation.

B. Verification Checklist

  • The project/configuration completes without an unresolved compile or device error.
  • Online, simulation or runtime values respond in the expected sequence for Machine Sequence in SCL.
  • Critical addresses, parameters, units and initial states are checked against the lab sheet.
  • The saved project can be reopened and the result reproduced without hidden manual correction.

C. If the Result Is Wrong

SymptomProbable causeDiagnostic checkCorrective action
Compile or configuration errorUnresolved device, tag, type, address or parameterOpen the first diagnostic entry and trace it to the configured objectCorrect the source item, compile again and save a new evidence record
No online/runtime responseWrong connection, command source, permissions or scan stateMonitor live values from input through logic to outputRestore the verified connection/state and repeat one controlled test
Unstable or unexpected valueScaling, initial state, timing or version mismatchCompare raw and engineering values and review the installed versionCorrect scaling/state, reset the lab safely and retest

D. Student Evidence Record

Environment

Record software version, controller/device firmware, driver and license status.

Project evidence

Save the project/archive name, modified block/object and parameter list.

Runtime evidence

Capture a verified screenshot, trend, alarm, tag table or measured value.

Conclusion

Write the pass condition, fault tested, correction made and final observation.

VERIFIED SCREENSHOT / TREND / TAG-TABLE EVIDENCE
Insert a real capture from the learner's lab. Do not use a fabricated software screenshot.
PracticalMachine Sequence in SCLPass conditionObserved result matches the stated objective and can be repeated.
Evidence filename________________Trainer / self-check________________

Expected Result

SCL sequence logic moves through machine steps in the correct order.

P18

Softwell Digital Practical Manual

Practical 18 - SCL Diagnostics Watch Table

Philosophy: Open the software, open the Softwell manual, and perform the practical.

SCL ProgrammingPLC LogicFunctionsAutomation
Software: TIA Portal with SCL / Structured Control Language editor
Setup: Engineering laptop, PLC simulator or training PLC, sample I/O tags

A. Step-by-Step Procedure

01
STEP 01
Create a watch table for SCL block inputs, outputs and static variables.
v
02
STEP 02
Add key variables such as StepNo, RunMemory and FaultCode.
v
03
STEP 03
Go online or start simulation.
v
04
STEP 04
Force or modify inputs carefully as per trainer instruction.
v
05
STEP 05
Observe how SCL variables change during execution.

B. Verification Checklist

  • The project/configuration completes without an unresolved compile or device error.
  • Online, simulation or runtime values respond in the expected sequence for SCL Diagnostics Watch Table.
  • Critical addresses, parameters, units and initial states are checked against the lab sheet.
  • The saved project can be reopened and the result reproduced without hidden manual correction.

C. If the Result Is Wrong

SymptomProbable causeDiagnostic checkCorrective action
Compile or configuration errorUnresolved device, tag, type, address or parameterOpen the first diagnostic entry and trace it to the configured objectCorrect the source item, compile again and save a new evidence record
No online/runtime responseWrong connection, command source, permissions or scan stateMonitor live values from input through logic to outputRestore the verified connection/state and repeat one controlled test
Unstable or unexpected valueScaling, initial state, timing or version mismatchCompare raw and engineering values and review the installed versionCorrect scaling/state, reset the lab safely and retest

D. Student Evidence Record

Environment

Record software version, controller/device firmware, driver and license status.

Project evidence

Save the project/archive name, modified block/object and parameter list.

Runtime evidence

Capture a verified screenshot, trend, alarm, tag table or measured value.

Conclusion

Write the pass condition, fault tested, correction made and final observation.

VERIFIED SCREENSHOT / TREND / TAG-TABLE EVIDENCE
Insert a real capture from the learner's lab. Do not use a fabricated software screenshot.
PracticalSCL Diagnostics Watch TablePass conditionObserved result matches the stated objective and can be repeated.
Evidence filename________________Trainer / self-check________________

Expected Result

Watch table helps diagnose SCL logic and internal variables.

P19

Softwell Digital Practical Manual

Practical 19 - Optimize and Comment SCL Code

Philosophy: Open the software, open the Softwell manual, and perform the practical.

SCL ProgrammingPLC LogicFunctionsAutomation
Software: TIA Portal with SCL / Structured Control Language editor
Setup: Engineering laptop, PLC simulator or training PLC, sample I/O tags

A. Step-by-Step Procedure

01
STEP 01
Open one completed SCL block.
v
02
STEP 02
Add clear comments above major logic sections.
v
03
STEP 03
Rename unclear variables to meaningful names.
v
04
STEP 04
Remove unused temporary variables.
v
05
STEP 05
Compile and confirm zero errors after cleanup.

B. Verification Checklist

  • The project/configuration completes without an unresolved compile or device error.
  • Online, simulation or runtime values respond in the expected sequence for Optimize and Comment SCL Code.
  • Critical addresses, parameters, units and initial states are checked against the lab sheet.
  • The saved project can be reopened and the result reproduced without hidden manual correction.

C. If the Result Is Wrong

SymptomProbable causeDiagnostic checkCorrective action
Compile or configuration errorUnresolved device, tag, type, address or parameterOpen the first diagnostic entry and trace it to the configured objectCorrect the source item, compile again and save a new evidence record
No online/runtime responseWrong connection, command source, permissions or scan stateMonitor live values from input through logic to outputRestore the verified connection/state and repeat one controlled test
Unstable or unexpected valueScaling, initial state, timing or version mismatchCompare raw and engineering values and review the installed versionCorrect scaling/state, reset the lab safely and retest

D. Student Evidence Record

Environment

Record software version, controller/device firmware, driver and license status.

Project evidence

Save the project/archive name, modified block/object and parameter list.

Runtime evidence

Capture a verified screenshot, trend, alarm, tag table or measured value.

Conclusion

Write the pass condition, fault tested, correction made and final observation.

VERIFIED SCREENSHOT / TREND / TAG-TABLE EVIDENCE
Insert a real capture from the learner's lab. Do not use a fabricated software screenshot.
PracticalOptimize and Comment SCL CodePass conditionObserved result matches the stated objective and can be repeated.
Evidence filename________________Trainer / self-check________________

Expected Result

SCL code is readable, maintainable and compiles cleanly.

P20

Softwell Digital Practical Manual

Practical 20 - Final SCL Programming Project

Philosophy: Open the software, open the Softwell manual, and perform the practical.

SCL ProgrammingPLC LogicFunctionsAutomation
Software: TIA Portal with SCL / Structured Control Language editor
Setup: Engineering laptop, PLC simulator or training PLC, sample I/O tags

A. Step-by-Step Procedure

01
STEP 01
Build one integrated SCL project using motor latch, analog scaling and sequence logic.
v
02
STEP 02
Add fault code generation and watch table diagnostics.
v
03
STEP 03
Call all required SCL blocks from the main program.
v
04
STEP 04
Run simulation or hardware test for the complete flow.
v
05
STEP 05
Archive the final project and record expected results.

B. Verification Checklist

  • The project/configuration completes without an unresolved compile or device error.
  • Online, simulation or runtime values respond in the expected sequence for Final SCL Programming Project.
  • Critical addresses, parameters, units and initial states are checked against the lab sheet.
  • The saved project can be reopened and the result reproduced without hidden manual correction.

C. If the Result Is Wrong

SymptomProbable causeDiagnostic checkCorrective action
Compile or configuration errorUnresolved device, tag, type, address or parameterOpen the first diagnostic entry and trace it to the configured objectCorrect the source item, compile again and save a new evidence record
No online/runtime responseWrong connection, command source, permissions or scan stateMonitor live values from input through logic to outputRestore the verified connection/state and repeat one controlled test
Unstable or unexpected valueScaling, initial state, timing or version mismatchCompare raw and engineering values and review the installed versionCorrect scaling/state, reset the lab safely and retest

D. Student Evidence Record

Environment

Record software version, controller/device firmware, driver and license status.

Project evidence

Save the project/archive name, modified block/object and parameter list.

Runtime evidence

Capture a verified screenshot, trend, alarm, tag table or measured value.

Conclusion

Write the pass condition, fault tested, correction made and final observation.

VERIFIED SCREENSHOT / TREND / TAG-TABLE EVIDENCE
Insert a real capture from the learner's lab. Do not use a fabricated software screenshot.
PracticalFinal SCL Programming ProjectPass conditionObserved result matches the stated objective and can be repeated.
Evidence filename________________Trainer / self-check________________

Expected Result

Final SCL project demonstrates reusable functions, function blocks, diagnostics and complete machine logic.

SCL Language Reference — Copyable Examples

This page is the language/reference companion. Compile each example in a controlled TIA Portal training project and record the CPU/TIA version used.

Typed FC interface

Use explicit input/output types and a deterministic return path.

FUNCTION "ScaleRaw" : Real
VAR_INPUT
  RawValue : Int;
  RawMin   : Int;
  RawMax   : Int;
END_VAR
ScaleRaw := (INT_TO_REAL(RawValue - RawMin) * 100.0) / INT_TO_REAL(RawMax - RawMin);
END_FUNCTION

Verify: Test minimum, midpoint, maximum and divide-by-zero prevention in the calling block.

Interlock with clear priority

Separate permissive, start and fault-reset decisions.

MotorPermissive := EStopHealthy AND GuardClosed AND NOT Overload;
IF ResetFault AND OverloadHealthy THEN
  MotorFault := FALSE;
END_IF;
MotorRun := StartCmd AND MotorPermissive AND NOT MotorFault;

Verify: Force each permissive false and confirm the output drops safely.

FOR loop across an array

Process a bounded array and avoid an index outside the declared range.

Total := 0.0;
FOR Index := 0 TO 9 DO
  Total := Total + Samples[Index];
END_FOR;
Average := Total / 10.0;

Verify: Test known sample values and compare the calculated average.

CASE state machine

Keep transitions visible and define a safe default state.

CASE State OF
  0: IF StartCmd THEN State := 10; END_IF;
  10: IF StepDone THEN State := 20; END_IF;
  20: IF CycleDone THEN State := 0; END_IF;
ELSE
  State := 0;
END_CASE;

Verify: Test normal transitions, reset and an invalid state.

Rising-edge command

Run a one-scan action from a maintained operator command.

StartEdge(CLK := StartCmd);
IF StartEdge.Q THEN
  BatchCounter := BatchCounter + 1;
END_IF;

Verify: Hold StartCmd true and confirm the counter changes only once.

Reusable alarm limits

Create consistent warning and trip logic with hysteresis handled by the caller.

HighWarning := ProcessValue >= WarningLimit;
HighTrip := ProcessValue >= TripLimit;
StatusCode := 0;
IF HighWarning THEN StatusCode := 1; END_IF;
IF HighTrip THEN StatusCode := 2; END_IF;

Verify: Sweep the process value through both limits and record transitions.

Practice, Viva and Mini-Project

  • Practice: Modify one input, predict the result, execute the code and compare the output.
  • Viva: Explain the data flow, failure behavior, safe-use boundary and recovery method.
  • Mini-project: Combine at least three examples into one reviewed, versioned solution with an evidence pack.
  • Acceptance: A second learner can run the saved solution and reproduce the documented result.

Before You Start: Prerequisites, Tested Version, Safety and Evidence

This manual is a practical training workbook, not a substitute for the installed product manual or the site's approved engineering procedure. Record the exact software, firmware, license and hardware before following a step because menus and supported functions can vary by release.

Tested-version planning scope: Confirm TIA Portal V18 or V19 SCL, the target controller firmware, data-access mode and current IEC-style syntax. Enter the exact lab-tested software, firmware and hardware in the record below before course delivery; never assume cross-version compatibility.

Environment record

Software build, firmware, device catalog, driver, communication interface and license status.

Safe lab boundary

Use an isolated training system. Follow electrical, mechanical, process and cybersecurity controls before energizing or downloading.

Evidence pack

Keep the source project, parameter/code export, screenshot/trend, fault test, correction and final pass result.

Technical review

Last reviewed by Softwell Automation Technical Training Team on 17 July 2026.

FieldLearner recordVerification
Software / firmware________________Matches the training device and official compatibility information
Project / backup________________Saved before and after the practical
Pass evidence________________Runtime value, trend, alarm, diagnostic or report attached
Fault tested________________Symptom, cause, check and corrective action documented

Practice, Viva and Extension Challenge

Practice

Change one approved input or parameter, predict the result, execute the test and explain any difference.

Viva

Explain the data flow, safety boundary, first diagnostic check and recovery method without opening the answer.

Extension challenge

Add one useful function while preserving the original pass criteria, alarm behavior and rollback path.

Graded mini-project

Combine at least three practicals, submit a versioned project and evidence pack, and demonstrate repeatable recovery.

Siemens SCL Language Reference four-stage practical lab, runtime verification, diagnosis and backup workflow
Instructional workflow diagram: complete configuration, measurable verification, controlled diagnosis and recovery evidence in sequence.
Siemens Industry Online Support — official documentation

Content status: Substantively reviewed and expanded 17 July 2026. Verify release-specific details against the linked official documentation.

Verified learning pathway

Practise This Manual with Guidance

Use the manual with trainer-led practicals, software exercises and troubleshooting support.

Content reviewed: 17 July 2026

☎ Call WhatsApp ✉ Email Enquire Now