WinCC Tag Types Explained: Internal, Process, Structure & System Tags

Build a clean PLC-to-SCADA tag architecture in SIMATIC WinCC and understand when to use internal tags, structured tags and tags mapped directly to PLC addresses.

PLC ↔ WinCC data path Internal vs process tags Structured tag design Quality & diagnostics

Learning Overview

Part 1: Communication architecturePart 2: Tag-type selectionPart 3: Hands-on WinCC setupEstimated time: 120 minutes

Prerequisites / What You’ll Need

  • SIMATIC WinCC engineering environment or a test project
  • Siemens PLC or PLCSIM/test source with known tags
  • Basic knowledge of PLC addresses and symbolic tags
  • A non-production Runtime test window for communication checks
Terminology note

WinCC terminology varies by generation. In WinCC Classic, a PLC-connected variable is commonly described as a process/external tag. In this guide, “direct tag” means a WinCC tag mapped directly to a PLC address or symbolic PLC item. “Structured tag” refers to grouping based on a defined structure/type where supported.

  • Use internal tags for HMI-only state; do not waste PLC bandwidth on values that never leave Runtime.
  • Use process/direct tags when the value is owned by the controller and must reflect PLC quality.
  • Use structured organization for repeated equipment such as motors, valves, tanks and drives.
  • Tag naming, data type and ownership must be defined before graphics, alarms and scripts are built.

What are the tag types in WinCC?

WinCC uses three practical tag types. An internal tag lives only in WinCC Runtime and has no PLC address. A process tag (often called a direct or external tag) is linked through a communication connection to one PLC item. A structure tag is an instance of a structure type whose members map to repeated PLC equipment such as motors, pumps or valves. WinCC also creates system tags, internal tags whose names start with @, such as @CurrentUser, which Runtime fills in by itself.

1. PLC-SCADA Communication Architecture in WinCC

A reliable WinCC project starts with a clear ownership model. The PLC owns machine logic, interlocks, sequence state and field values. WinCC visualizes and supervises those values, adds operator commands, alarms, trends and reports, and may hold HMI-only state. The communication driver and connection object sit between the two systems.

Recommended data flow

Field Device → PLC Tag/DB → WinCC Connection → WinCC Process Tag → Screen / Alarm / Trend / Script

Animated PLC-SCADA data flow in WinCCProcess values flow from the field device to the PLC, through the WinCC communication connection into a process tag and on to screens, alarms and trends. Operator commands flow back from Runtime to the PLC, where PLC logic validates them. Read path: process value, PLC to WinCC Field devicesensor, contactorPLCtag / data blockConnectionchannel + driverWinCC tagprocess tagRuntimescreen, alarm, trend Write path: operator command to PLC, validated by PLC logic
Read values travel left to right through one communication connection; operator writes travel back and must be checked by PLC logic. The connection object is the single point every process tag depends on.

Before creating hundreds of tags, define the controller, connection type, PLC namespace, update requirement and whether each value is read-only, write-enabled or purely internal to the HMI.

2. WinCC Tag Types at a Glance

Tag typeData ownerTypical usePLC traffic
Internal tagWinCC RuntimeNavigation state, temporary values, script flags, local calculationsNone
System tag (@…)WinCC Runtime, written automaticallyLogged-on user, computer name, redundancy state, script loadNone
Process / direct tagPLC or external deviceMotor status, temperature, setpoint, VFD speed, alarmsYes
Structured tag / grouped structureUsually PLC + WinCC type definitionRepeated motor/valve/tank objects with consistent membersDepends on members
Animated comparison of WinCC internal, process and structure tagsInternal tags stay inside WinCC Runtime and create no PLC traffic. Process tags carry one PLC value each across the connection. Structure tags carry a group of members, such as a pump interface, as one typed object.PLC (S7-1500)WinCC RuntimeInternal tagno PLC address, no network traffic—HMI_ScreenNoProcess tagone value per PLC itemDB_IO.LT201_pctTank01.Level_PVStructure tagmembers travel as one typed objectDB_Pumps.P201P201.* (PumpIF)
Where each WinCC tag type lives and what crosses the network: nothing for internal tags, one value per process tag, and a typed member set for a structure tag.

3. Internal Tags: Values Owned by WinCC

Internal tags exist in WinCC and are not addressed through a PLC connection. They are ideal for values such as selected screen number, report start/end time, local simulation flags, operator-entered temporary values or a script result that does not need to be stored in the controller.

  • Choose a data type that matches the HMI function.
  • Use a clear prefix or folder so internal values are not mistaken for PLC tags.
  • Do not use an internal tag to imitate a real PLC status. That can create a dangerous visual mismatch.
  • If the value must survive Runtime restart, confirm the required persistence mechanism instead of assuming all internal tags are retained.
HMI.Screen.SelectedUnit     INT
HMI.Report.StartTime        DATETIME
HMI.Simulation.Enable      BOOL
HMI.Popup.ActiveMotor      STRING

4. WinCC System Tags (@ Tags)

Besides the tags you create, WinCC creates system tags by itself. They are internal tags whose names start with @, and WinCC Runtime writes their values: who is logged on, which computer the screen runs on, the state of a redundant server pair, how busy the script engine is. They need no PLC connection, cost no PLC bandwidth and appear in Tag Management under Internal tags, grouped by the WinCC component that owns them.

Animated WinCC system tags driving a Runtime header barWinCC Runtime updates system tags such as @CurrentUser, @CurrentUserName, @LocalMachineName, @RedundantServerState, @RM_MASTER and @SCRIPT_COUNT_ACTIONS_IN_QUEUES. When operator1 logs on, the header bar shows the user. When the redundant partner is lost, @RedundantServerState changes from 1 (Master) to 4 (Standalone) and back when the pair is restored.WinCC Runtime fills these tags by itself: no PLC, no configurationSystem tagLive value@CurrentUser(no user)operator1@CurrentUserNameRavi Patil@LocalMachineNameWINCC-SRV1@RedundantServerState1 Master4 Standalone1 Master@RM_MASTER111@SCRIPT_COUNT_ACTIONS…0310Overview.pdl – header barUserStationServerLog on to operateoperator1 (Ravi Patil)WINCC-SRV1MasterStandalone – partner lostMasterButtons locked until a user logs onSetpoint changes logged with @CurrentUserRedundancy alarm raised for the operatorRedundant pair restored
System tags are internal tags that WinCC Runtime keeps up to date. Bind them to I/O fields for a header bar showing user, station and server state, or read them in scripts. The values shown are examples.

Most useful WinCC system tags

System tagValueWhat it tells youTypical use
@CurrentUserTextLogin name of the user logged on in RuntimeHeader bar, operator logging, access checks in scripts
@CurrentUserNameTextFull name of the logged-on userReadable user display, reports
@LocalMachineNameTextName of the computer running this RuntimeStation-specific screens and logging on multi-user systems
@DatasourceNameRTTextName of the Runtime databaseSQL and OLE DB connection strings for reports
@ServerNameTextName of the WinCC server in a client/server projectShowing which server a client uses
@RedundantServerStateNumber0 undefined, 1 master, 2 standby, 3 fault, 4 standaloneRedundancy status display and alarms
@RM_MASTER, @RM_MASTER_NAMEBinary, textWhether this server is master, and the master’s nameRun a task only on the master server
@SCRIPT_COUNT_TAGS, @SCRIPT_COUNT_ACTIONS_IN_QUEUES, @SCRIPT_COUNT_REQUESTS_IN_QUEUESNumberLoad on the script engine: requested tags, queued actions and requestsFinding overloaded global scripts

Redundancy tags only carry meaningful values when the WinCC Redundancy option is licensed and configured. Their use is covered in WinCC system architecture and redundancy, and logging on users in WinCC user administration.

Read system tags in screens and scripts

In Graphics Designer, link an I/O field in output mode directly to @CurrentUser or @LocalMachineName. In scripts, read them like any other tag:

' VBScript (e.g. on a setpoint change): record who changed it and where
Dim sUser, sStation
sUser    = HMIRuntime.Tags("@CurrentUser").Read
sStation = HMIRuntime.Tags("@LocalMachineName").Read
HMIRuntime.Trace "Speed_SP changed by " & sUser & " on " & sStation & vbNewLine
/* C script in a button event: block a command when nobody is logged on */
char* user = GetTagChar("@CurrentUser");
if (user == NULL || strlen(user) == 0) {
   printf("Command blocked: no user logged on\r\n");
   return;
}

Rules for working with system tags

  • Never create your own tags with an @ prefix. The prefix is reserved for WinCC, and a name clash causes confusing behaviour.
  • Treat system tags as read-only. WinCC overwrites them, so use your own internal tag for anything you need to set.
  • Do not delete, rename or archive system tags as if they were project tags.
  • On client/server systems, check on which station a tag such as @CurrentUser is evaluated before you use it for access decisions.
  • There is no single system tag that proves every PLC value is fresh. For PLC health, combine tag quality (see the tag quality section below) with a PLC heartbeat counter that WinCC watches for changes.
Not the same thing

The System Info channel is a separate WinCC driver for values such as date and time, CPU load and free disk space. You add it like a communication driver and create tags under it. Those are ordinary tags of that channel, not @ system tags.

5. Direct / Process Tags Mapped to the PLC

A process tag represents a real item in the PLC or another external device. Configure the WinCC communication connection first, then create the tag with the correct controller data type and address. For a Siemens PLC, prefer symbolic addressing when the engineering environment and driver support it because the tag name follows the controller object rather than depending on a fixed byte/bit address.

Write access: only expose HMI writes for parameters and commands that the PLC logic is designed to validate. Never treat a writable SCADA tag as a substitute for PLC interlocks or safety logic.
Animated WinCC write to a PLC setpoint with PLC range validationA setpoint of 1200 rpm written from WinCC passes the PLC range check and is stored. A setpoint of 9999 rpm is rejected by PLC logic and never reaches the data block.WinCC I/O fieldoperator enters Speed_SPPLC data blockPLC rangecheck0 – 1500 rpm1200 rpm9999 rpmAccepted: inside the PLC limitRejected by PLC logic: out of rangeSpeed_SP = 0Speed_SP = 1200Writable process tag: the PLC decides, not the screen
Expose a writable process tag only when PLC logic validates the value. Here 1200 rpm is accepted and 9999 rpm is rejected before it reaches the data block.

Typical process tags include Motor01.RunFeedback, Tank01.Level_PV, Furnace.Temp_Set, VFD01.Speed_Act and AlarmDB.HighTemp.

6. Structured Tags for Repeated Equipment

Structured organization becomes valuable when many pieces of equipment share the same data model. Instead of engineering unrelated tag names for every motor, define a repeatable member set and apply consistent naming across the controller and SCADA.

Motor01.CmdStart
Motor01.CmdStop
Motor01.RunFB
Motor01.Fault
Motor01.Current_A
Motor01.Speed_Pct
Motor01.ModeAuto
Animated WinCC structure type creating Motor01, Motor02 and Motor03 instancesA single structure type named MotorType defines the members CmdStart, CmdStop, RunFB, Fault, Current_A and Speed_Pct. Three motor instances are created from it, each with the identical member set.Structure typeMotorType.CmdStart.CmdStop.RunFB.Fault.Current_A.Speed_PctMotor01.CmdStart.CmdStop.RunFB.Fault.Current_A.Speed_PctMotor02.CmdStart.CmdStop.RunFB.Fault.Current_A.Speed_PctMotor03.CmdStart.CmdStop.RunFB.Fault.Current_A.Speed_PctDefine the member set once, create one instance per motor
One structure type, many identical instances. Every motor gets the same member names, so one faceplate, one alarm template and one script work for all of them.

The same member pattern can be reused for Motor02, Motor03 and so on. This improves faceplate engineering, alarm templates, scripting and maintenance. Where the WinCC generation supports structure types or integrated PLC structures, map the controller structure carefully and verify every member data type after compile/download.

7. Symbolic vs Absolute Addressing

ApproachExampleAdvantageRisk
SymbolicDB_Motor01.RunFBReadable and easier to maintainRequires supported symbolic integration
AbsoluteDB10.DBX2.0Explicit physical addressCan break if DB layout changes
InternalHMI.ScreenIndexNo PLC dependencyNot a live controller value
Animated symbolic vs absolute addressing after a data block changeDB10 holds Speed_SP at byte 0, RunFB at byte 2.0 and Current_A at byte 4. When a new Int member called Mode is inserted at the top, every member shifts by two bytes. The absolute WinCC tag DB10.DBX2.0 now reads a bit of Speed_SP, while the symbolic tag DB_Motor01.RunFB still follows RunFB.DB_Motor01 (DB10, standard access)0.02.04.06.0Speed_SPIntRunFBBoolCurrent_AIntMode (new member)IntAbsolute WinCC tagDB10.DBX2.0reads RunFB ✓now reads a bit of Speed_SP ✗Symbolic WinCC tagDB_Motor01.RunFBfollows the member ✓A new member is inserted at the top of the DB. Every byte offset after it moves by 2.
Why symbolic addressing survives PLC changes: inserting one member shifts every absolute offset after it, but a symbolic tag follows the member name. Optimized data blocks have no fixed absolute offsets at all.

For optimized data blocks, do not assume an absolute address exists in the same way as a non-optimized DB. Use the addressing method supported by the PLC/WinCC combination and keep the PLC and HMI engineering model aligned.

8. Tag Quality, Timestamp and Communication Status

A screen showing the last good numeric value can be misleading if communication has failed. For critical values, engineer visual quality indication or communication status. Distinguish a process value of zero from a tag that is bad, stale or unavailable.

  • Monitor connection health and controller reachability.
  • Use quality information where exposed by the WinCC interface.
  • Record communication alarms separately from process alarms.
  • Do not automatically overwrite a bad process value with zero.
Animated WinCC tag quality during a PLC communication failureWhile the PLC link is healthy both displays show 72.4 degrees with good quality. When the link is lost, the wrong design shows 0.0 degrees, which looks like a real reading, while the right design shows hash marks and a bad-quality warning.PLCTemperature_PVlink lostWrong: bad value replaced with zero72.4 °C0.0 °Cquality: goodlooks valid, but it is notRight: quality shown to the operator72.4 °C### °Cquality: goodbad quality: no connection
A communication failure must never look like a real process value. Show bad quality and a placeholder instead of forcing the value to zero.

9. Naming and Folder Strategy

A scalable project uses predictable names. One useful pattern is Area.Equipment.Signal or an equivalent hierarchy supported by the project. Keep commands, feedbacks, setpoints and process values distinguishable.

WinCC tag naming hierarchy Area.Equipment.SignalThe area Line1 contains the equipment Conv01, which has five signals: CmdStart as a command, RunFB as feedback, Fault as an alarm, Speed_SP as a setpoint and Speed_PV as a process value.Line1Conv01Line1.Conv01.CmdStartcommandLine1.Conv01.RunFBfeedbackLine1.Conv01.FaultalarmLine1.Conv01.Speed_SPsetpointLine1.Conv01.Speed_PVprocess value
The Area.Equipment.Signal pattern makes every tag self-describing: you can tell a command from a feedback, alarm, setpoint or process value from its name alone.
Line1.Conv01.CmdStart
Line1.Conv01.RunFB
Line1.Conv01.Fault
Line1.Conv01.Speed_SP
Line1.Conv01.Speed_PV

Use the same engineering vocabulary in PLC tags, WinCC tags, alarm text and documentation. Consistency reduces commissioning time more than clever abbreviations.

10. Step-by-Step WinCC Communication Workflow

  1. Confirm PLC IP address, reachable network and controller operating state.
  2. Create the correct WinCC communication channel/driver and PLC connection.
  3. Test one known Boolean and one known analog value before bulk tag creation.
  4. Create internal HMI tags separately from PLC process tags.
  5. Build a structured naming convention for repeated equipment.
  6. Verify data types and write permissions.
  7. Place tags on a diagnostic screen showing value, quality and command status.
  8. Only after communication is proven, map tags into alarms, trends, recipes and scripts.

11. Creating, Copying and Pasting Tags in WinCC Explorer V8.1

In WinCC Explorer V8.1, double-clicking Tag Management opens it in WinCC Configuration Studio. The window has three areas: the navigation tree on the left (drivers, connections, tag groups and structure tags), the data grid in the middle where every row is one tag, and the Properties pane on the right for the selected row. The grid works much like a spreadsheet, which is what makes copy, paste and drag-fill so fast.

Create an internal tag

  1. In the navigation tree, select Internal tags. For a tidy project, right-click it and create a group such as HMI.
  2. In the grid, click the Name cell of the empty row at the bottom and type the name, for example HMI_ScreenNo.
  3. Choose the data type, for example Unsigned 8-bit value for a screen number.
  4. Set a start value or limits in the Properties pane only if the HMI function needs them.

Create a process tag on an S7-1500 connection

  1. Right-click Tag Management and choose Add new driver, then SIMATIC S7-1200, S7-1500 Channel.
  2. Expand the channel, right-click the OMS+ unit and create a new connection, for example PLC_1. Enter the CPU IP address in the connection properties.
  3. Right-click the connection and create a tag group, for example Motors.
  4. Load the PLC symbols with AS Symbols (see Stage 4 of the lab below), or type the tag in the grid and set its data type and address.
  5. Start Runtime and prove one tag on a diagnostic screen before you create the rest.

Copy, paste and drag-fill tags

The grid supports Ctrl+C and Ctrl+V. Select one or more complete rows by clicking the row headers, copy them, click the empty row of the same or another tag group and paste. Tag names must be unique in a project, so a pasted copy of an existing tag receives a changed name; rename it straight away to match your convention.

Animated drag-fill of WinCC tags in Configuration StudioIn WinCC Configuration Studio the tag Motor01_RunFB is selected in the Motors group of connection PLC_1. Dragging the fill handle down creates Motor02_RunFB to Motor05_RunFB with the same data type, connection and group.WinCC Configuration Studio – Tag ManagementTag ManagementInternal tagsSIMATIC S7-1200, S7-1500…OMS+PLC_1MotorsStructure tagsNameData typeConnectionGroupMotor01_RunFBBinary tagPLC_1MotorsMotor02_RunFBBinary tagPLC_1MotorsMotor03_RunFBBinary tagPLC_1MotorsMotor04_RunFBBinary tagPLC_1MotorsMotor05_RunFBBinary tagPLC_1Motors4 tags created, names incrementedDrag the fill handle down, like in Excel
Drag-fill in the Tag Management grid: one finished row becomes a series of tags. The number in the name increases, while data type, connection and group are copied.
  • Drag-fill: select the cells of a finished row and drag the small square at the bottom-right corner of the selection downwards. A trailing number in the name is increased (Motor01_RunFB becomes Motor02_RunFB); the other cells are copied.
  • Fill one column only: select just the Data type cell and drag it down to give a whole block of tags the same type.
  • Check the connection: each process tag belongs to exactly one connection. After pasting into another group, confirm the Connection column.
  • Addresses: for symbolic S7-1500 tags, load members from AS Symbols rather than drag-filling addresses, and check every address after any fill.

Create tags in bulk from Excel

For dozens of similar tags, plan the list in Excel first. Put the columns in the same order as the Tag Management grid, select the data rows without the header, copy them, click the Name cell of the empty grid row and paste. Configuration Studio can also export an editor’s data to Excel and import it back from the shortcut menu in the navigation area; the exact menu names vary slightly between WinCC versions.

Animated copy of a tag list from Excel into WinCC Tag ManagementFour tag names, Pump01_Running, Pump01_Fault, Pump02_Running and Pump02_Fault, are copied with Ctrl+C from an Excel sheet and pasted with Ctrl+V into the WinCC Configuration Studio grid, followed by a check of data type and connection.Excel tag listTag Management gridPump01_RunningPump01_RunningPump01_FaultPump01_FaultPump02_RunningPump02_RunningPump02_FaultPump02_FaultCtrl+CCtrl+VNow check data type and connectionBulk tags: plan in Excel, paste into the grid, then verify
Copy rows from Excel and paste them straight into the Tag Management grid. The columns must be in the same order as the grid, and every pasted row still needs a check of data type and connection.
Name            Data type     Connection  Group
Pump01_Running  Binary tag    PLC_1       Pumps
Pump01_Fault    Binary tag    PLC_1       Pumps
Pump02_Running  Binary tag    PLC_1       Pumps
Pump02_Fault    Binary tag    PLC_1       Pumps

Paste two rows as a test before you paste the full list, then check the data type, connection and address of the test rows online.

Copy structure tags instead of loose tags

For repeated equipment, multiply structure instances rather than single tags. Create the structure type once under Structure tags, for example PumpIF with the members Cmd_Start, Cmd_Stop, RunCmd and Running. Then create one tag of that structure type per pump in the connection’s tag group. WinCC creates every member tag of the instance for you, so P202 is a complete copy of P201 with a new name, and one faceplate serves both.

Before you paste 200 tags: copy and paste repeat a mistake as quickly as a correct tag. Prove one tag of each kind online, then multiply it.

12. Practical Lab: Motor + Analog Value

Create a small test with one motor and one analog process value. The PLC should expose Motor_RunFB, Motor_Fault, Speed_SP and Temperature_PV. WinCC should also contain an internal tag named HMI_SelectedMotor.

TagTypeDirectionExpected test
Motor_RunFBPLC process tagPLC → SCADAChanges with controller feedback
Motor_FaultPLC process tagPLC → SCADAAlarm/indicator follows fault bit
Speed_SPPLC process tagSCADA → PLCPLC validation accepts valid range
Temperature_PVPLC process tagPLC → SCADAAnalog value updates continuously
HMI_SelectedMotorInternal tagWinCC onlyNo PLC address configured

13. Troubleshooting WinCC Tag Communication

SymptomLikely causeCheck
All PLC tags badConnection/network issueIP, route, driver, PLC state, firewall
Only one tag badAddress/type mismatchPLC symbol, DB member, WinCC type
Read works, write failsAccess/logic restrictionPLC permissions, command logic, write path
Value freezesConnection interrupted or acquisition issueQuality, update cycle, diagnostics
Structured member wrongLayout/type mismatchStructure definition and member mapping

WinCC Tag Architecture Verification Lab

Hands-on lab
Before you start
  • Use a training or test system, not a live production plant.
  • Document the starting PLC/WinCC state and expected result.
  • Verify communication and backups before applying engineering changes.
1

Prove the connection

Read one Boolean and one analog PLC value before bulk engineering.

Both values update with good communication status.
2

Separate ownership

Create one internal tag and confirm it has no PLC address.

Internal HMI state changes without network traffic.
3

Build repeated structure

Map a motor signal set using consistent member names.

Faceplate-ready tag organization is available.
4

Test safe writes

Write a bounded speed setpoint through PLC validation logic.

Valid values are accepted; invalid values are rejected by PLC logic.

Lab Manual: Tag Types from Field to WinCC Runtime

The sections above explain the three tag types. This lab builds them on one tank with two pumps, with the pump logic in both ladder and SCL, and tests tag quality live.

Lab manual flow: field input to tested HMI screenSix stages: field device and PLC tag, input mapping to DB_IO, PLC logic, HMI tags, graphics linking, and perform and test.1Field + tags%IW112 %I9.7level, feedbacks2Input mappingFC_InputMapping→ DB_IO3LogicFB_Pump ×2LAD + SCL4WinCC tagsprocess, structured+ internal5Graphicsfaceplatesper instance6Perform + testSimulatortag qualityAddress rule for every lesson: %I only in FC_InputMapping, %Q only in FC_OutputMapping, symbolic DB members everywhere else – including the HMI.
Six-stage lab flow used in every lesson of the Softwell lab manual series.

Stage 1 – Field wiring and PLC tags

PLC tagAddressTypeDevice / comment
LT201_Raw%IW112IntLevel 4–20 mA = 0 – 100 %
LSL201_OK%I9.7BoolLow-level switch, 1 = water present
P201_Running / P202_Running%I10.0 / %I10.1BoolContactor feedbacks
K201 / K202%Q4.3 / %Q4.4BoolPump contactors

Stage 2 – Input mapping into DB_IO

"DB_IO".LT201_pct  := SCALE_X(MIN := 0.0, MAX := 100.0, VALUE := NORM_X(MIN := 0, VALUE := "LT201_Raw", MAX := 27648));
"DB_IO".LSL201_OK  := "LSL201_OK";
"DB_IO".P201_Running := "P201_Running";  "DB_IO".P202_Running := "P202_Running";

Stage 3 – PLC logic in ladder and SCL

FB_Pump instance networks for P201 (P202 identical with its own instance)Ladder diagram: Network 1 — Run command from the WinCC structure tag P201.Cmd_Start; Network 2 — Running status from feedbackNetwork 1 — Run command from the WinCC structure tag P201.Cmd_StartCmd_Start#Iface (P201)Cmd_Stop#IfaceLSL201_OK"DB_IO"RunCmd#IfaceRunCmdseal-inNetwork 2 — Running status from feedbackP201_Running"DB_IO"Running#Iface
FB_Pump networks in ladder, called once per pump with its own interface structure.

The same logic in SCL – use whichever your plant standard prefers; both write the same DB members that WinCC reads:

// FB_Pump – InOut #Iface : UDT_PumpIF (Cmd_Start, Cmd_Stop, RunCmd, Running, Level)
#Iface.RunCmd  := (#Iface.Cmd_Start OR #Iface.RunCmd) AND NOT #Iface.Cmd_Stop AND #LowLevelOK;
#Iface.Running := #Feedback;
#Iface.Cmd_Start := FALSE;  #Iface.Cmd_Stop := FALSE;

// OB1 – one call per pump; WinCC sees "DB_Pumps".P201 and "DB_Pumps".P202 with the same structure
"IDB_P201"(LowLevelOK := "DB_IO".LSL201_OK, Feedback := "DB_IO".P201_Running, Iface := "DB_Pumps".P201);
"IDB_P202"(LowLevelOK := "DB_IO".LSL201_OK, Feedback := "DB_IO".P202_Running, Iface := "DB_Pumps".P202);
"DB_Pumps".LT201_pct := "DB_IO".LT201_pct;

Stage 4 – Link PLC tags to WinCC: three tag types

In Tag Management add the SIMATIC S7-1200, S7-1500 Channel, create a connection with the CPU IP address, then use AS Symbols to load the PLC symbols and drag the DB members you need into a tag group. The DB members must have Accessible from HMI ticked in TIA Portal. Names and menus can differ slightly between WinCC versions.

WinCC tagData typeConnection / addressUsed by
ScreenNoUnsigned 8-bitInternal tag (no connection)Screen navigation
DB_Pumps_LT201_pctFloating-point 32-bitProcess tag, symbolicLevel field and trend
P201 / P202 (structure type PumpIF)StructureCmd_Start, Cmd_Stop, RunCmd, Running → DB_Pumps.P201 / .P202Faceplates

Stage 5 – Link the graphics

#ObjectPropertiesTag / event
①Pump faceplate (copied per instance)Buttons write Cmd_Start/Cmd_Stop of the instance; lamp on RunningP201.*, P202.*
②I/O field levelOutput, 999.9 %DB_Pumps_LT201_pct
③Connection statusDynamic on tag quality or the connection status tagTag Management diagnostics

Faceplate events and dynamics are detailed in WinCC buttons and lamps.

Stage 6 – Perform and test: tag types and tag quality

Start the pumps through their structure instances, change the internal screen tag, then cut the PROFINET connection and compare how internal, process and structured tags behave.

Tank and PLC
WinCC Runtime · Tag diagnostics
TagDiag.pdlTag Management
TagTypeAddressValueQuality

Frequently Asked Questions

What is an internal tag in WinCC?

An internal tag is owned by WinCC Runtime and has no PLC communication address. Use it for HMI-only state, temporary values and local script logic.

What is a direct tag in WinCC?

In this guide, a direct tag means a WinCC process tag mapped directly to a PLC address or symbolic PLC item. Exact terminology differs by WinCC generation.

When should structured tags be used?

Use structured organization when repeated equipment shares the same signal model, such as multiple motors, valves, drives or tanks.

Should I use symbolic or absolute PLC addressing?

Prefer symbolic addressing where the PLC and WinCC combination supports it. Absolute addressing can be valid but is more sensitive to DB layout changes.

Why is tag quality important?

Quality distinguishes a true process value from a stale or unavailable value caused by communication failure.

Why do my WinCC process tags show bad quality?

If every process tag is bad, check the connection first: PLC IP address, network route, communication driver and CPU operating state. If only one tag is bad, check that the PLC symbol still exists, that its data type matches the WinCC tag and that the DB member is accessible from HMI.

What does 'Accessible from HMI' mean in TIA Portal?

It is a property of each data block member in TIA Portal. Only members with this option enabled are offered to WinCC when you load PLC symbols, so an unticked member cannot be linked as a process or structure tag.

Do internal tags count towards the WinCC tag licence?

In WinCC Classic, the Runtime licence is counted on external (process) tags. Internal tags do not need a PLC connection and are not counted as licensed process tags; check the licensing notes for your exact WinCC version.

How do I copy and paste tags in WinCC Explorer V8.1?

Open Tag Management, which opens in WinCC Configuration Studio. Select complete rows in the grid, press Ctrl+C, click the empty row of the target tag group and press Ctrl+V. Tag names must be unique, so rename pasted tags to your convention and check the connection and data type of each row.

How do I create many WinCC tags with incrementing names?

Finish one tag row, select its cells and drag the fill handle at the bottom-right corner of the selection downwards. WinCC increases the trailing number in the name and copies the other cells, for example Motor01_RunFB to Motor05_RunFB.

Can I create WinCC tags from an Excel sheet?

Yes. Arrange the Excel columns in the same order as the Tag Management grid, copy the data rows and paste them into the empty row of the grid. Test with two rows first, then check the data type, connection and address of the pasted tags.

What are system tags in WinCC?

System tags are internal tags whose names start with @. WinCC creates and updates them itself, for example @CurrentUser for the logged-on user, @LocalMachineName for the computer name and @RedundantServerState for the state of a redundant server. They need no PLC connection and should be treated as read-only.

How do I show the logged-in user on a WinCC screen?

Insert an I/O field in Graphics Designer, set it to output and link it to the system tag @CurrentUser, or @CurrentUserName for the full name. In VBScript you can read the same value with HMIRuntime.Tags("@CurrentUser").Read.

Verified learning pathway

Learn WinCC Tag Engineering with a Trainer

Practise PLC-SCADA communication, tag management, faceplates and diagnostics on Siemens PLC trainer kits in Softwell’s WinCC training.

Content reviewed: 10 November 2026 by Bhawesh Kumar Singh

☎ Call WhatsApp ✉ Email Enquire Now