WinCC Runtime Advanced Alarms & Event Messages: Complete TIA Portal Configuration Guide: Complete Contents
- 1. Start with an Alarm Philosophy
- 2. Build Deterministic Alarm Logic in the PLC
- 3. Configure Discrete Alarms
- 4. Configure Analog Alarms
- 5. Use Alarm Classes and Priorities
- 6. Acknowledgement and State Transitions
- 7. Configure the Runtime Alarm View
- 8. Alarm Logging and Runtime History
- 9. PLC-to-HMI Alarm Example
- 10. Alarm Commissioning Test
- 11. Common Alarm Problems
Practical WinCC Runtime Advanced Engineering Guide
1. Start with an Alarm Philosophy
2. Build Deterministic Alarm Logic in the PLC
3. Configure Discrete Alarms
4. Configure Analog Alarms
5. Use Alarm Classes and Priorities
6. Acknowledgement and State Transitions
7. Configure the Runtime Alarm View
8. Alarm Logging and Runtime History
9. PLC-to-HMI Alarm Example
// SCL-style PLC alarm preparation
Alarm_HighTemp := TempPV > TempHighLimit;
Alarm_MotorFault := MotorFaultInput OR DriveFault;
Alarm_CommLoss := NOT RemoteIO_Healthy;
Map these Boolean states to WinCC discrete alarms with clear text such as “Furnace 02 temperature above high limit” or “Conveyor 03 drive fault — check VFD diagnostics”.10. Alarm Commissioning Test
11. Common Alarm Problems
| Problem | Typical cause | Action |
|---|---|---|
| Alarm never appears | Wrong trigger tag/bit | Watch PLC bit and HMI tag online |
| Alarm chatters | No hysteresis/filtering | Stabilize condition in PLC/process logic |
| Wrong text/equipment | Copy/paste configuration | Audit message-to-tag mapping |
| Acknowledgement unclear | Poor state/display setup | Test active/ack/cleared lifecycle |
WinCC Runtime Advanced Hands-On Lab
Use a non-production PLC/HMI project, document the test conditions, and verify every HMI behavior against the PLC watch table or diagnostics. The objective is not only to make the screen work, but to prove that the engineer can diagnose a deliberate fault and recover the system methodically.
Frequently Asked Questions
What alarms can WinCC Runtime Advanced display?
It can be engineered to display discrete/event alarms and process/limit-related messages, with alarm classes, acknowledgement behavior and Runtime alarm views.
Should alarm logic be in the PLC or HMI?
Critical process conditions are best owned by the PLC. The HMI should visualize, acknowledge and log the condition according to the alarm philosophy.
Why do alarms chatter in Runtime?
The source condition may be oscillating around a limit. Add suitable hysteresis, filtering or delay in the process/PLC logic instead of trying to hide the problem only in the HMI.
Does acknowledgement clear the fault?
No. Acknowledgement confirms the operator has seen the message; the process fault clears only when its actual source condition is removed.