Download and Restore a Backup to a SINAMICS G120

Check before you click, practise the full restore in a STARTER-style trainer, and prove it survives a power cycle.

2,500+ engineers trained 4.9/5 Google rating 21+ years, Chinchwad, Pune Next batch: contact for dates
Quick answer

Download writes the offline project from the PC into the drive. In STARTER: verify the project name → upload the current drive first → Connect → Target device → Download to target device (overwrite all) → Copy RAM to ROM (p0971 = 1) → power-cycle and verify. The control unit type must match the backup, and the firmware should.

  • Download is destructive and has no undo.
  • Match the CU type; match the firmware where possible.
  • Without Copy RAM to ROM, the restore is lost at power-off.
  • Re-check the PROFINET name and IP after a restore.

Download Overwrites — Check Before You Click

A restore usually happens on the worst day of a shift: a failed drive, a replacement on the panel and the line stopped. With the wrong project open, one failed drive becomes two.

Verify the STARTER project name before downloading animationA project named for Line 3 opened at Line 2 must not be downloaded; when the name matches the machine and the current drive has been uploaded, the download proceeds.STARTERLine3_Conveyor3CULine2 · Conv. 3Title bar says Line3 — you are at Line2 ✕Stop: wrong project, a download would create a second failed driveSTARTERLine2_Conveyor3CULine2 · Conv. 3Name read aloud and matches ✓ · current drive uploaded ✓Now download: PC → drive, overwrites everything
Two habits: read the title bar out loud, and upload the drive you are about to overwrite, even if it is faulty.

Compatibility: What Must Match

G120 backup compatibility check animationThree cases cycle: a CU240E-2 PN backup to a CU240B-2 is refused; a minor firmware step usually works; a different motor needs new nameplate data.Backup CU240E-2 PN → target CU240B-2Control unit✕Firmware—Power module—Motor—Safety—Download refused or partial: never mix CU typesSame CU, FW 4.7 → 4.7 SPControl unit✓Firmware≈Power module✓Motor✓Safety—Minor firmware step usually works; check rejected parametersSame drive, different motor fittedControl unit✓Firmware✓Power module✓Motor⚠Safety—Re-enter nameplate data, or the new motor gets the old motor’s protection
The motor row causes silent damage: the drive runs fine until the motor overheats.
ItemRequirementIf it differs
Control unit typeMust match exactlyRefused or partial load
FirmwareShould match; minor step usually OKUnknown parameters rejected
Power moduleShould match rating and typeLimits recalculated: verify them
MotorSame motor, or new nameplate dataWrong protection: silent overheating
Safety configurationHandled separatelyNeeds its own acceptance test

Practise drive replacement before you need it

Hands-on STARTER backup, restore and device replacement on live SINAMICS hardware — Pune or online.

Book a Free Demo Class

The Download Sequence (Try It)

Restore the replacement drive below. Choose overwrite all parameters so no old macro or BICO settings survive. The demo also runs the classic mistake of skipping Copy RAM to ROM.

●●● STARTER-style restore trainer · open project Line2_Conveyor3 · OFFLINE
⚙ Drive (CU240E-2 PN)
RAM p1120 =
ROM p1120 =
state:
backup p1120 = 8.0 s
A replacement drive at factory defaults. Restore it.
  1. Project name verified
  2. Pre-restore upload saved
  3. Online
  4. Downloaded (overwrite all)
  5. Copied RAM to ROM
  6. Survived power cycle

Simplified trainer, not Siemens software. The demo also shows the classic failure: skipping Copy RAM to ROM.

Copy RAM to ROM — The Step People Miss

Copy RAM to ROM after download animationA download fills RAM only; a power cycle without p0971 returns the drive to factory defaults; running p0971 = 1 makes the restore survive.RAM (working)p1120 = 8.0 sROMp1120 = 10.0 s (default)Download completeRAM = backup · ROM = factoryRAM (working)p1120 = 10.0 s (default)ROMp1120 = 10.0 s (default)⚡power cyclePower cycle without p0971Drive comes back as factory default ✕RAM (working)p1120 = 8.0 sROMp1120 = 8.0 s⚡power cycleDownload → p0971 = 1 → power cycleSettings survive ✓
Do not accept “the download said it succeeded”: power-cycle and re-read a parameter you know was restored.

Post-Restore Checklist

Post-restore checklist and PROFINET device name animationSeven checks tick off in order; a restored drive keeping the original PROFINET name causes a station failure until it is renamed for its position.1. Motor nameplate vs physical motor✓2. Direction on a slow jog✓3. PROFINET name and IP✓4. p0015 vs terminal wiring✓5. Ramps and current limit✓6. Fault-free start and stop✓7. Fresh upload = new known-good backup✓PLC expects“conveyor4”restored drive says“conveyor3”Station failure ✕PLC expects“conveyor4”renamed drive“conveyor4”Station OK ✓
The backup carries the original drive’s identity, so set the PROFINET name and IP for this position.
CheckWhy
Motor nameplate dataThe backup describes the original motor
Direction on a slow jogCheap to check, expensive under load
PROFINET name and IPMust match this position in the controller
p0015 vs terminal wiringA restored macro reassigns every terminal
Ramps and current limitNo current-limiting on a normal start
Fault-free start and stopEnd-to-end proof
Fresh uploadYour new known-good backup

Hands-On Lab: Restore a Drive from Backup

Hands-on
Before you start
    '+LABPRE+'
1

Mark a value

Note p1120, change it to an obviously different value, and save with p0971 = 1.

The drive now differs from the backup in one known way.
2

Factory reset

Set p0010 = 30 then p0970 = 1.

A “new replacement” at factory defaults.
3

Verify the project

Open the backup and read the title bar out loud.

You can name the machine and drive it belongs to.
4

Connect and download

Connect, then Target device → Download to target device, overwriting all parameters.

The download completes (an offline/online difference warning is expected).
5

Copy RAM to ROM, then power-cycle

Set p0971 = 1, power down fully, then power up.

p1120 shows the backup value.
6

Skip the save once, on purpose

Reset, download again without p0971, then power-cycle.

The drive is back at factory defaults. You won’t forget p0971 again.
7

Work the checklist

Restore properly, then check motor data, a slow jog, p0015 and the PROFINET name.

Clean start, ramp and stop, and no station failure.
Checkpoint — how to know you did it right

'+CHECK+'

Frequently asked questions

What is the difference between download and upload in STARTER?

Download writes your PC project into the drive and overwrites what is there. Upload, shown as “Load to PG”, reads the drive into your project and changes nothing on the drive. Both names are from the PC’s point of view.

Can I restore a backup onto a different control unit type?

No. The control unit type must match: a CU240E-2 PN parameter set will not load correctly into a CU240B-2. Firmware should also match, though a minor version step usually works. Record both with every backup.

Why did my restored drive lose its settings after a power cycle?

Copy RAM to ROM was never run. A download writes into working memory only. Set p0971 = 1 after the download, then power-cycle and check a known parameter before leaving the machine.

What should I check after restoring a drive?

Motor nameplate data against the physical motor, direction on a slow jog, PROFINET device name and IP, p0015 against the actual terminal wiring, ramps and current limit, and a fault-free start and stop. Then take a fresh upload as the new known-good backup.

Why does the PLC report a station failure after a restore?

The backup carries the original drive’s PROFINET device name and IP. If the replacement sits at a different position, set the name and address the controller expects for that position.

Should I back up a drive I am about to replace, even if it is faulty?

Yes. It is the only record of how that drive was actually configured, and there is no undo for a download. It takes two minutes.

Reviewed by Bhawesh Kumar Singh Industrial Automation Trainer and Industry 4.0 Consultant · Softwell Automation · 21+ years industry experience

Get the full syllabus + free demo class

Share your details — a Softwell training advisor will call you within 24 hours with batch dates, fees and hardware access options.

No spam. Used only to share course details for this enquiry.

Learn with practical industrial examples

Join live online, Pune classroom or corporate in-plant automation training.

Request Course Details
Verified learning pathway

Turn This Concept into a Practical Skill

Apply this topic through PLC, SCADA, networking or Industry 4.0 laboratory exercises.

Content reviewed: 29 October 2026

☎ Call WhatsApp ✉ Email Enquire Now