SIMATIC Starter V5.7 SINAMICS G120
Handwritten Manual

Notebook-style practical training pattern for SINAMICS G120 VFD commissioning using STARTER V5.7, CU240E-2, USB/Ethernet, macros, PROFINET, Modbus RTU and terminal control.

5 Days / 40 Hours
M-Step Practical Notes
Parameter + Wiring Focus
Mobile + Print Friendly

Notebook Pattern
Step-by-Step
Drive Manual

✓ Connect → Upload → Macro → Test → Backup

SOFTWELL VFD LEVEL 01
01Connection & First Commissioning02Drive Macros: Fixed Speed & Analog Reference03Macro 7 PROFINET PLC Communication04Macro 21 Modbus RTU / USS Communication05Macro 17–20 Two-Wire / Three-Wire Control
DAY 01

Softwell SINAMICS G120 — Handwritten M-Step Manual

Connection & First Commissioning

Practical Outcome: Connect SIMATIC STARTER V5.7 with SINAMICS G120 via USB/Ethernet, upload parameters, compare online/offline and complete quick commissioning.

STARTER V5.7USB PC AdapterEthernet / PN-IEUpload to PG/PCCompare OnlineMotor ID Run
Trainer Note: Complete every step in SIMATIC STARTER V5.7 with safe wiring, correct parameter backup, online monitoring and final commissioning checklist.
01
Step 1. Install / connect USB PC Adapter A2 or Ethernet cable to CU240E-2 / CU240E-2-PN.
02
Step 2. Open STARTER V5.7 and set PG/PC Interface: PC Adapter USB A2 or PN/IE according to connection.
03
Step 3. Create new project: SINAMICS G120, CU240E-2 / CU240E-2-PN, firmware V4.9 or available firmware.
04
Step 4. Use Accessible Nodes / Connect to target system and confirm drive appears online.
05
Step 5. Upload all parameters from drive to PC using Load to PG/PC and save project backup.
06
Step 6. Compare online/offline parameters and note any differences before changing drive settings.
07
Step 7. Run Quick Commissioning Wizard and enter motor nameplate data: voltage, current, kW, cos phi, Hz and RPM.
08
Step 8. Select control mode, application class, command source and ramp-up/ramp-down time.
09
Step 9. Perform Motor Data Identification Run after mechanical safety check.
10
Step 10. Save parameters to EEPROM using p0971 = 1 and archive final commissioned project.

Parameter / Wiring Reference

p0010 = 30  // Factory reset preparation
p0970 = 1   // Factory reset
p0304 = 400 // Rated motor voltage
p0305 = 2.05// Rated motor current
p0307 = 0.75// Rated motor power
p0310 = 50  // Rated frequency
p0311 = 1395// Rated speed
p0971 = 1   // Save RAM to EEPROM

Daily Practice / Viva

Prepare one screenshot or handwritten note for communication setting, parameter list, wiring check, troubleshooting point and final test result of Day 01.

DAY 02

Softwell SINAMICS G120 — Handwritten M-Step Manual

Drive Macros: Fixed Speed & Analog Reference

Practical Outcome: Commission SINAMICS G120 using macro-based control for terminal commands, fixed speeds and analog speed reference.

Macro 1Macro 3Macro 12DI/DO WiringAI 0–10VRamp Settings
Trainer Note: Complete every step in SIMATIC STARTER V5.7 with safe wiring, correct parameter backup, online monitoring and final commissioning checklist.
01
Step 1. Open Quick Commissioning and understand drive macros as ready-made command/reference templates.
02
Step 2. Select Macro 1 for simple terminal start/stop with basic speed reference.
03
Step 3. Wire digital input commands as per selected macro and verify DI status in STARTER diagnostics.
04
Step 4. Set minimum and maximum frequency limits such as p1080 and p1082.
05
Step 5. Configure ramp-up p1120 and ramp-down p1121 according to machine requirement.
06
Step 6. Select Macro 3 / fixed speed configuration and assign DI inputs to fixed frequency selection.
07
Step 7. Configure fixed speeds and test each DI combination safely.
08
Step 8. Select Macro 12 for analog reference using AI input.
09
Step 9. Scale 0–10V / 4–20mA analog input and verify r0755 / actual reference value.
10
Step 10. Document macro number, terminal wiring, speed values and final running test result.

Parameter / Wiring Reference

p0015 = 1    // Macro 1 example
p1080 = 0.00 // Minimum frequency
p1082 = 50.0 // Maximum frequency
p1120 = 5.0  // Ramp-up time
p1121 = 5.0  // Ramp-down time
p1001 = 10.0 // Fixed speed 1
p1002 = 25.0 // Fixed speed 2
p1003 = 40.0 // Fixed speed 3

Daily Practice / Viva

Prepare one screenshot or handwritten note for communication setting, parameter list, wiring check, troubleshooting point and final test result of Day 02.

DAY 03

Softwell SINAMICS G120 — Handwritten M-Step Manual

Macro 7 PROFINET PLC Communication

Practical Outcome: Configure G120 with Compact / Siemens PLC style fieldbus control using PROFINET, telegram, control word, status word and speed reference.

PROFINETTelegram 1Control WordStatus WordPLC CommandDiagnostics
Trainer Note: Complete every step in SIMATIC STARTER V5.7 with safe wiring, correct parameter backup, online monitoring and final commissioning checklist.
01
Step 1. Assign PROFINET device name to CU240E-2-PN and verify exact name in PLC hardware configuration.
02
Step 2. Set IP address, subnet and network connection using Accessible Nodes or STARTER online settings.
03
Step 3. Select Macro 7 / fieldbus control for PROFINET communication.
04
Step 4. Configure telegram 1 or project-specified PROFIdrive telegram.
05
Step 5. Map PLC output words to drive control word and speed setpoint.
06
Step 6. Map drive input words to PLC status word and actual speed feedback.
07
Step 7. Test STW1 bits: ON/OFF1, enable operation, fault acknowledge and direction as per PLC logic.
08
Step 8. Monitor ZSW1 status word to confirm ready, operation enabled, fault and warning status.
09
Step 9. Scale PLC speed setpoint to drive reference and verify actual frequency feedback.
10
Step 10. Save STARTER project and prepare PLC-drive commissioning checklist.

Parameter / Wiring Reference

// Telegram 1 common word mapping
PLC -> Drive PZD1 = STW1 Control Word
PLC -> Drive PZD2 = Speed Setpoint
Drive -> PLC PZD1 = ZSW1 Status Word
Drive -> PLC PZD2 = Actual Speed

STW1 bit 0 = ON/OFF1
STW1 bit 1 = OFF2 enable
STW1 bit 2 = OFF3 enable
STW1 bit 7 = Fault acknowledge

Daily Practice / Viva

Prepare one screenshot or handwritten note for communication setting, parameter list, wiring check, troubleshooting point and final test result of Day 03.

DAY 04

Softwell SINAMICS G120 — Handwritten M-Step Manual

Macro 21 Modbus RTU / USS Communication

Practical Outcome: Configure RS485 communication for Modbus RTU or USS and test register-based control, status and speed reference.

Macro 21RS485Modbus RTUUSSRegistersBaud Rate
Trainer Note: Complete every step in SIMATIC STARTER V5.7 with safe wiring, correct parameter backup, online monitoring and final commissioning checklist.
01
Step 1. Identify CU240E-2 RS485 terminals and prepare shielded twisted pair communication wiring.
02
Step 2. Set slave address, baud rate, parity, stop bits and protocol type according to master device.
03
Step 3. Select Macro 21 for Modbus RTU / USS communication as per training setup.
04
Step 4. Configure command source and speed reference from serial communication.
05
Step 5. Understand Modbus holding registers used for command word, reference and status values.
06
Step 6. Test communication using Modbus master software or PLC Modbus block.
07
Step 7. Write ON command and speed setpoint from master and verify drive response.
08
Step 8. Read actual frequency, current, status word and fault code from drive.
09
Step 9. Troubleshoot no-response errors: A/B polarity, address mismatch, baud/parity mismatch and termination resistor.
10
Step 10. Document final Modbus register map and verified test values.

Parameter / Wiring Reference

// Typical serial settings for lab
Protocol      = Modbus RTU / USS
Slave address = 3
Baud rate     = 9600 or 19200
Parity        = Even
Stop bits     = 1
Cable         = Shielded twisted pair RS485
Termination   = ON at both ends only

Daily Practice / Viva

Prepare one screenshot or handwritten note for communication setting, parameter list, wiring check, troubleshooting point and final test result of Day 04.

DAY 05

Softwell SINAMICS G120 — Handwritten M-Step Manual

Macro 17–20 Two-Wire / Three-Wire Control

Practical Outcome: Commission terminal-based two-wire and three-wire control circuits with safe start/stop, jog, direction, fault reset and final viva.

Macro 17Macro 18Macro 19Macro 202-Wire3-Wire
Trainer Note: Complete every step in SIMATIC STARTER V5.7 with safe wiring, correct parameter backup, online monitoring and final commissioning checklist.
01
Step 1. Explain difference between two-wire maintained command and three-wire momentary start/stop command.
02
Step 2. Select Macro 17 / 18 / 19 / 20 according to required terminal control method.
03
Step 3. Wire start, stop, forward, reverse, jog and fault reset inputs as per macro terminal diagram.
04
Step 4. Check DI status online before enabling motor output.
05
Step 5. Test two-wire command: maintained input ON runs drive, OFF stops drive.
06
Step 6. Test three-wire command: momentary start latches internal run, stop input breaks run command.
07
Step 7. Add direction command and verify reverse operation only if motor/mechanical system allows it.
08
Step 8. Test fault acknowledge input and confirm drive resets only after fault source is clear.
09
Step 9. Prepare final backup, parameter list, wiring checklist and safety checklist.
10
Step 10. Final viva: connection methods, macro selection, motor ID, EEPROM save, control word/status word and troubleshooting.

Parameter / Wiring Reference

// Final handover checklist
[ ] Correct macro selected
[ ] Motor nameplate data verified
[ ] Ramp-up / ramp-down tested
[ ] DI/AI wiring checked
[ ] PROFINET or Modbus tested if used
[ ] Fault reset verified
[ ] p0971 = 1 EEPROM save done
[ ] STARTER backup archived

Daily Practice / Viva

Prepare one screenshot or handwritten note for communication setting, parameter list, wiring check, troubleshooting point and final test result of Day 05.

☎ Call 🟢 WhatsApp ✉ Enquire Now