Answer six questions, try the interactive selector, size by current, not kW, and confirm in the TIA Selection Tool.

2,500+ engineers trained 4.9/5 Google rating 21+ years, Chinchwad, Pune Next batch: contact for dates
Quick answer

Start with the motion: continuous speed means a VFD (V20, G120C, G120, G120X, G220); positioning means a servo (V90, S200, S210, S120). Then filter by power and supply, application (pump vs heavy start), communication, safety and mounting. Size by motor current and overload class, not kW, and confirm in the TIA Selection Tool.

  • Continuous speed → VFD. Positioning → servo.
  • Pumps/fans: G120X or V20. Machines: G120C or G220.
  • Size by current: LO for pumps, HO for heavy starts.
  • Need STO or PROFINET? Not V20.

The SINAMICS Portfolio at a Glance

SINAMICS portfolio map animationDrive families placed by power range and performance: V20, G120C, G120X, G120, G220 and G115D/G120D for continuous motion, and V90, S200, S210 and S120 for positioning and servo.power (kW, log scale)performance / dynamics0.11101001000V20 · basic VFDG120C · compact VFDG120X · pumps & fansG120 · modular VFDG220 · new-gen VFDG115D/G120D · distributed IP65V90 · basic servoS200 · standard servoS210 · dynamic servoS120 · high-end systemcontinuous motion ↓ · positioning ↑
Ranges are approximate catalogue figures and change; confirm the current range in the TIA Selection Tool.

Six Questions That Decide the Drive

#QuestionWhy it matters
1Continuous speed or positioning?VFD family vs servo family
2Motor power, current and supply?Power range, 1-ph vs 3-ph, frame size
3What load? Pump/fan vs heavy startControl mode and overload class (LO/HO)
4How is it controlled?Terminals, Modbus/USS, PROFINET
5Which safety function?None, STO on terminals, PROFIsafe/extended
6Where is it mounted?Cabinet IP20 vs on-machine IP65

Not sure which drive fits?

Send us your motor and application, and our trainers will suggest a SINAMICS family. Or learn selection and commissioning hands-on.

Get Selection Help

Interactive SINAMICS Drive Selector with MLFB Number

Answer the questions and the selector proposes the family and, for G120C and V20, the exact MLFB (article number), decoded and sized by current at your overload duty.

1
2
3
0.37 kW7.5132630 kW
4
5
6
7
8
9
10
Recommended family

MLFB / article number
Check data sheet / price in SiePortal ↗
Control
Engineering
Alternatives

Article numbers are generated from the published G120C and V20 numbering for 400 V units, and the drive is sized by current at the chosen overload. This is a training aid: confirm the final order number, options and accessories in the Siemens TIA Selection Tool or SiePortal before ordering.

Sizing: Current and Overload, Not kW

Size a drive by current and overload, not kWThree cases: a pump fits a low-overload rating; a conveyor with heavy starting torque needs the high-overload rating; two motors on long cable need summed current and derating.Pump, 7.5 kW motor, 14.5 AMotor current needed14.5 ADrive rating (LO)16.5 ALow overload (LO) 7.5 kW rating ≥ 14.5 A ✓Conveyor with heavy start, 7.5 kW motorMotor current needed14.5 ADrive rating (HO)13.2 ASame 7.5 kW drive at HO is only 13.2 A ✕ → heavy start needs the next size upLong cable 120 m, 2 motors on one driveMotor current needed29 ADrive rating (candidate)26 ASum the currents (29 A) + cable derating: 26 A candidate ✕ → next size up, check output reactor
Select by motor rated current and duty (LO vs HO), then apply derating for altitude, ambient, pulse frequency and cable length.
DutyTypical loadsSelect
Low overload (LO)Pumps, fans, compressorsDrive LO current ≥ motor rated current
High overload (HO)Conveyors, crushers, mixers, hoistsDrive HO current ≥ motor current (often one size up)
DeratingAltitude, ambient, pulse frequency, long cables, multi-motorApply manufacturer derating, then re-check

Family Comparison

FamilyApprox. powerBest forCommunicationSafetyEngineering
V200.12–30 kWBasic pumps, fans, conveyorsTerminals, USS/Modbus RTU—BOP / Smart Access
G120C0.55–132 kWCompact machine drivePROFINET/EtherNet/IP, PROFIBUS or USS/Modbus variantsSTOStartdrive / STARTER
G120X0.75–630 kWPumps, fans, compressorsPROFINET, Modbus, BACnet (variants)STOStartdrive
G1200.55–250 kWModular CU + PM, encoder, safetyPROFINET, PROFIBUS, othersSTO to extended (CU-dependent)Startdrive / STARTER
G2200.55–160 kWNew-gen high performancePROFINETSTO/SS1 terminalsStartdrive
G115D / G120D≈0.37–7.5 kWDistributed IP65 conveyorsPROFINET / AS-i (variants)STO (variants)Startdrive
V90≈0.05–7 kWBasic servo, pulse train / PNPTI, PROFINETSTOV-ASSISTANT / Startdrive
S2000.1–7 kWStandard servoPROFINET or PTISTOStartdrive / web server
S210≤ 7 kWDynamic single-axis servoPROFINETSTO, extended via PROFIsafeStartdrive
S120up to MW rangeMulti-axis, high-end systemsPROFINET, PROFIBUS, DRIVE-CLiQExtendedStartdrive / STARTER

Ranges and options are approximate and change between releases; verify in the current Siemens catalogue or TIA Selection Tool. Compare servo and VFD in Servo Drive vs VFD.

Plant Architecture: Standardise the Network

Mixed SINAMICS drives on one PROFINET network animationAn S7 PLC on PROFINET controls a G120X pump, a G120C conveyor, a G220 extruder and an S210 indexing axis, all engineered in Startdrive.PLCS7-1200 / 1500PROFINETG120XpumpG120CconveyorG220extruderS210indexing axisOne engineering tool: Startdrive in TIA Portal, telegrams on PROFINET ✓Speed axes use telegram 1/20 · the servo uses telegram 105 with SINAMICS technology objects
Standardising on PROFINET and Startdrive keeps spares, training and diagnostics simple across the plant.

Hands-On Lab: Select and Size a Drive

Hands-on
Before you start
    '+LABPRE+'
1

Collect the motor data

Read the nameplate: voltage, current, power, speed, Δ/Y and cooling.

A complete motor record.
2

Describe the duty

Note start torque, cycle, overload, ambient and cable length.

You can say LO or HO, and list any derating.
3

Run the selector

Use the selector above to get a family and alternatives.

A candidate family with a reason.
4

Confirm in the TIA Selection Tool

Enter the motor and duty, and pick communication, safety and options.

An order number and accessory list.
5

Check the result

Compare drive current at the chosen overload with the motor current, after derating.

Margin is positive and documented.
Checkpoint — how to know you did it right

'+CHECK+'

Frequently asked questions

How is a SINAMICS G120C MLFB (article number) built?

For the 400 V G120C it reads 6SL3210-1KE + power code + filter + fieldbus + version: for example 6SL3210-1KE21-7AF1 is 7.5 kW (LO), A = integrated class A filter, F = PROFINET/EtherNet/IP, version 1. U means no filter, P is PROFIBUS DP and B is USS/Modbus RTU. Always confirm the final number in the TIA Selection Tool or SiePortal.

How do I choose between SINAMICS V20 and G120C?

Choose V20 for simple, cost-sensitive pumps, fans and conveyors on terminals or Modbus/USS up to about 30 kW. Choose G120C when you need PROFINET, STO on terminals, vector control or more power (up to 132 kW). V20 has no STO.

When should I use G120X instead of G120C?

G120X is the pump, fan and compressor specialist up to 630 kW, with infrastructure functions such as multi-pump control. For general machines, conveyors and mixed loads, G120C or G120 is the usual choice.

What is SINAMICS G220?

G220 is Siemens’ newer-generation general-purpose converter, positioned above G120 for higher performance and digitalisation. It is engineered in Startdrive (TIA Portal) and suits demanding machines such as extruders and high-torque drives.

Should I select a drive by kW or by current?

By current. Match or exceed the motor’s rated current at the right overload class: low overload (LO) for pumps and fans, high overload (HO) for heavy starting loads such as conveyors and crushers. Then apply derating for ambient, altitude, pulse frequency and cable length.

When do I need a servo drive instead of a VFD?

When the task is positioning, fast indexing or tightly synchronised motion with high dynamics. Use S200 or S210 for single axes up to about 7 kW, S120 for multi-axis or higher power. A VFD is right for continuous speed control.

How do I get the exact order number?

Use the Siemens TIA Selection Tool or the SINAMICS Selector app with your motor data, duty, supply, communication, safety and options. A selection guide narrows the family; the tool confirms the exact rating and accessories.

Reviewed by Bhawesh Kumar Singh Industrial Automation Trainer and Industry 4.0 Consultant · Softwell Automation · 21+ years industry experience

Get the full syllabus + free demo class

Share your details — a Softwell training advisor will call you within 24 hours with batch dates, fees and hardware access options.

No spam. Used only to share course details for this enquiry.

Learn with practical industrial examples

Join live online, Pune classroom or corporate in-plant automation training.

Request Course Details
Verified learning pathway

Turn This Concept into a Practical Skill

Apply this topic through PLC, SCADA, networking or Industry 4.0 laboratory exercises.

Content reviewed: 29 October 2026

☎ Call WhatsApp ✉ Email Enquire Now