ABB ACS580 control macros: wiring, simulator and Drive Composer setup

A macro is a ready-made set of parameter defaults for one wiring style. Pick the closest one in 96.04, wire it as shown, check a handful of parameters in Drive Composer, and most of the commissioning is done. Open any macro below for its terminal map, wiring diagram and step-by-step setup.

2,500+ engineers trained 4.9/5 Google rating 21+ years, Chinchwad, Pune Next batch: contact for dates
Quick answer

Select a macro with 96.04 Macro select and confirm it in 96.05. All macros start in scalar control except ABB standard (vector). Changing macro resets everything except motor data and changes what each terminal does.

Which macro do I need?

Answer three questions and we will open the matching macro below.

1. How is the drive started?

2. Where does the speed come from?

Prefer a table? Wiring → macro
You have…Start with
A selector switch and a potABB standard, or ABB standard (vector) for rpm and torque at low speed
Momentary start and stop buttons3-wire
Separate forward and reverse commandsAlternate
A PLC with digital outputs onlyMotor potentiometer
A local station plus a PLCHand/Auto
A 4–20 mA process transmitterPID, or Hand/PID for a manual fallback
Setpoint typed on the keypadPanel PID
Several pumps or fans from one drivePFC

Every input, every macro

Colour shows what each terminal does. Outputs are the same in every macro listed: AO1 output frequency, AO2 motor current, RO1 ready run, RO2 running, RO3 fault (-1). Click a macro name to open it.

Start / stopDirectionPresets, ramps, up/downRun enableControl-place selectReference / PIDNot configured
InputABB standardABB standard (vector)3-wireAlternateMotor potentiometerHand/AutoHand/PIDPID
AI1Frequency reference 1, 0–10 VSpeed reference 1, 0–10 VSpeed / frequency reference 1, 0–10 VSpeed / frequency reference 1, 0–10 VNot configuredAnalog reference for one control placeHand reference or PID setpoint, 0–10 VPID setpoint, 0–10 V
AI2Not configuredNot configuredNot configuredNot configuredNot configuredAnalog reference for the other control placeActual PID feedback, 4–20 mAActual PID feedback, 4–20 mA
DI1Stop (0) / Start (1)Stop (0) / Start (1)Start (pulse)Start forward (DI1 = DI2 → stop)Stop (0) / Start (1)Start/stop, HandStop (0) / Start (1), HandStop (0) / Start (1), PID
DI2Forward (0) / Reverse (1)Forward (0) / Reverse (1)Stop (pulse)Start reverseForward (0) / Reverse (1)Direction, HandHand (0) / PID (1) selectionConstant PID setpoint 1 (40.21)
DI3Constant frequency selectConstant speed selectForward (0) / Reverse (1)Constant speed / frequency selectReference upHand or Auto selectionConstant frequency selectConstant PID setpoint 2 (40.22)
DI4Constant frequency selectConstant speed selectConstant speed / frequency selectConstant speed / frequency selectReference downRun enableConstant frequency selectConstant frequency 1 (28.26)
DI5Ramp set 1 (0) / Ramp set 2 (1)Ramp set 1 (0) / Ramp set 2 (1)Constant speed / frequency selectRamp set 1 (0) / Ramp set 2 (1)Constant frequency / speed 1Direction, AutoRun enable; 0 stops the driveRun enable; 0 stops the drive
DI6Not configuredNot configuredNot configuredRun enable; 0 stops the driveRun enable; 0 stops the driveStart/stop, AutoStop (0) / Start (1), PIDNot configured
Not covered here

Panel PID (setpoint from the keypad, AI2 feedback, DI1 start/stop) and PFC (multi-pump and fan control) are taught in class with the full terminal map from the firmware manual.

Every macro: click to open wiring and Drive Composer steps

ABB standard96.04 = ABB standard

The factory-default macro: a general-purpose 2-wire setup with one signal for start/stop, one for direction, and three constant frequencies.

Control terminals X1–X3 · ABB standard macro (inputs that change most are highlighted)

2AI1Frequency reference 1, 0–10 V
5AI2Not configured
13DI1Stop (0) / Start (1)
14DI2Forward (0) / Reverse (1)
15DI3Constant frequency select
16DI4Constant frequency select
17DI5Ramp set 1 (0) / Ramp set 2 (1)
18DI6Not configured

Wiring diagram

Control terminalsField devicesFunction in this macro2AI1Frequency reference 1, 0–10 V3AGNDAnalog common4+10V10 V reference5AI2Not configured6AGNDAnalog common7AO1Output frequency, 0–20 mA8AO2Motor current, 0–20 mA9AGNDAnalog common10+24V24 V DC aux, max 250 mA11DGND24 V common12DCOMDigital input common13DI1Stop (0) / Start (1)14DI2Forward (0) / Reverse (1)15DI3Constant frequency select16DI4Constant frequency select17DI5Ramp set 1 (0) / Ramp set 2 (1)18DI6Not configured19–21RO1Ready run22–24RO2Running25–27RO3Fault (-1)factory jumper10 kΩ speed potRun switchFwd / Rev switchPreset select APreset select BRamp select
Wiring for the ABB standard macro. Digital inputs are fed from the drive’s own +24 V (terminal 10) with DGND–DCOM bridged by the factory jumper. Set S1 to U for 0–10 V on AI1 and S2 to I for 4–20 mA on AI2, matching 12.15 and 12.25.

Configure the ABB standard macro in Drive Composer

Drive Composer entry / pro
0 of 8 steps done
Before you start
  • ACS580 powered, STO terminals closed (factory jumpers in place)
  • PC with Drive Composer and a USB cable to the assistant control panel
  • Motor nameplate data and the wiring done as in the diagram
1

Connect

Plug a USB cable from the PC into the USB port on the drive's assistant control panel, open Drive Composer (entry or pro) and connect. The drive appears in the drive list.

2

Back up first

Save the current parameters to a file (entry) or take a full Backup (pro) so you can return to the old setup.

3

Enter motor data

Open Parameters › group 99 and enter 99.06–99.11 from the nameplate. Leave 99.04 on Scalar unless the load needs vector control.

4

Select the macro

Open group 96, set 96.04 Macro select to ABB standard, and confirm 96.05 Macro active shows the same name. Every non-motor parameter now returns to the macro defaults.

5

Check the I/O mapping

Open the parameters in the table below and confirm each one points to the input shown. Change only what your wiring differs on.

6

Tune ramps, presets and limits

Set acceleration and deceleration times, preset speeds or setpoints, and min/max limits in group 30 (30.11–30.14).

7

Test with the Monitor window

Add 01.06 Output frequency, 01.07 Motor current, 10.02 DI delayed status and 12.12 AI1 scaled value. Operate each switch and watch the matching bit and value change.

8

Save and document

Write 96.07 Parameter save manually = Save, then use Print to keep a PDF parameter record (as on the Softwell lab printouts). In pro, compare against the backup to list every change.

Expected result: 96.05 Macro active shows ABB standard, every row in the check table matches, and each switch changes the matching bit in 10.02 DI delayed status.

Check after selecting

ParameterNameShould read
20.03Ext1 in1 sourceDI1
20.04Ext1 in2 sourceDI2
28.11Ext1 frequency ref1AI1 scaled
28.22 / 28.23Constant frequency sel1 / sel2DI3 / DI4
28.71Freq ramp set selectionDI5
12.15 / 12.17–12.20AI1 unit, min, max, scalingV, 0–10 V → 0–50 Hz
ABB standard (vector)96.04 = ABB standard (vector)

The same 2-wire wiring as ABB standard, but the drive runs in vector control, so references and presets are speeds in rpm.

Control terminals X1–X3 · ABB standard (vector) macro (inputs that change most are highlighted)

2AI1Speed reference 1, 0–10 V
5AI2Not configured
13DI1Stop (0) / Start (1)
14DI2Forward (0) / Reverse (1)
15DI3Constant speed select
16DI4Constant speed select
17DI5Ramp set 1 (0) / Ramp set 2 (1)
18DI6Not configured

Wiring diagram

Control terminalsField devicesFunction in this macro2AI1Speed reference 1, 0–10 V3AGNDAnalog common4+10V10 V reference5AI2Not configured6AGNDAnalog common7AO1Output frequency, 0–20 mA8AO2Motor current, 0–20 mA9AGNDAnalog common10+24V24 V DC aux, max 250 mA11DGND24 V common12DCOMDigital input common13DI1Stop (0) / Start (1)14DI2Forward (0) / Reverse (1)15DI3Constant speed select16DI4Constant speed select17DI5Ramp set 1 (0) / Ramp set 2 (1)18DI6Not configured19–21RO1Ready run22–24RO2Running25–27RO3Fault (-1)factory jumper10 kΩ speed potRun switchFwd / Rev switchPreset select APreset select BRamp select
Wiring for the ABB standard (vector) macro. Digital inputs are fed from the drive’s own +24 V (terminal 10) with DGND–DCOM bridged by the factory jumper. Set S1 to U for 0–10 V on AI1 and S2 to I for 4–20 mA on AI2, matching 12.15 and 12.25.

Configure the ABB standard (vector) macro in Drive Composer

Drive Composer entry / pro
0 of 8 steps done
Before you start
  • ACS580 powered, STO terminals closed (factory jumpers in place)
  • PC with Drive Composer and a USB cable to the assistant control panel
  • Motor nameplate data and the wiring done as in the diagram
1

Connect

Plug a USB cable from the PC into the USB port on the drive's assistant control panel, open Drive Composer (entry or pro) and connect. The drive appears in the drive list.

2

Back up first

Save the current parameters to a file (entry) or take a full Backup (pro) so you can return to the old setup.

3

Enter motor data

Open Parameters › group 99 and enter 99.06–99.11 from the nameplate. Set 99.04 Motor control mode to Vector, then request an ID run in 99.13 and start the drive to run it.

4

Select the macro

Open group 96, set 96.04 Macro select to ABB standard (vector), and confirm 96.05 Macro active shows the same name. Every non-motor parameter now returns to the macro defaults.

5

Check the I/O mapping

Open the parameters in the table below and confirm each one points to the input shown. Change only what your wiring differs on.

6

Tune ramps, presets and limits

Set acceleration and deceleration times, preset speeds or setpoints, and min/max limits in group 30 (30.11–30.14).

7

Test with the Monitor window

Add 01.06 Output frequency, 01.07 Motor current, 10.02 DI delayed status and 12.12 AI1 scaled value. Operate each switch and watch the matching bit and value change.

8

Save and document

Write 96.07 Parameter save manually = Save, then use Print to keep a PDF parameter record (as on the Softwell lab printouts). In pro, compare against the backup to list every change.

Expected result: 96.05 Macro active shows ABB standard (vector), every row in the check table matches, and each switch changes the matching bit in 10.02 DI delayed status.

Check after selecting

ParameterNameShould read
20.03Ext1 in1 sourceDI1
20.04Ext1 in2 sourceDI2
22.11Ext1 speed ref1AI1 scaled
22.22 / 22.23Constant speed sel1 / sel2DI3 / DI4
23.11Ramp set selectionDI5
99.04Motor control modeVector
3-wire96.04 = 3-wire

Built for momentary push-buttons: one pulse starts the drive, another pulse stops it, with a direction input and three constant speeds.

Control terminals X1–X3 · 3-wire macro (inputs that change most are highlighted)

2AI1Speed / frequency reference 1, 0–10 V
5AI2Not configured
13DI1Start (pulse)
14DI2Stop (pulse)
15DI3Forward (0) / Reverse (1)
16DI4Constant speed / frequency select
17DI5Constant speed / frequency select
18DI6Not configured

Wiring diagram

Control terminalsField devicesFunction in this macro2AI1Speed / frequency reference 1, 0–10 V3AGNDAnalog common4+10V10 V reference5AI2Not configured6AGNDAnalog common7AO1Output frequency, 0–20 mA8AO2Motor current, 0–20 mA9AGNDAnalog common10+24V24 V DC aux, max 250 mA11DGND24 V common12DCOMDigital input common13DI1Start (pulse)14DI2Stop (pulse)15DI3Forward (0) / Reverse (1)16DI4Constant speed / frequency select17DI5Constant speed / frequency select18DI6Not configured19–21RO1Ready run22–24RO2Running25–27RO3Fault (-1)factory jumper10 kΩ speed potStart push-buttonStop push-buttonFwd / Rev switchPreset select APreset select B
Wiring for the 3-wire macro. Digital inputs are fed from the drive’s own +24 V (terminal 10) with DGND–DCOM bridged by the factory jumper. Set S1 to U for 0–10 V on AI1 and S2 to I for 4–20 mA on AI2, matching 12.15 and 12.25.

Configure the 3-wire macro in Drive Composer

Drive Composer entry / pro
0 of 8 steps done
Before you start
  • ACS580 powered, STO terminals closed (factory jumpers in place)
  • PC with Drive Composer and a USB cable to the assistant control panel
  • Motor nameplate data and the wiring done as in the diagram
1

Connect

Plug a USB cable from the PC into the USB port on the drive's assistant control panel, open Drive Composer (entry or pro) and connect. The drive appears in the drive list.

2

Back up first

Save the current parameters to a file (entry) or take a full Backup (pro) so you can return to the old setup.

3

Enter motor data

Open Parameters › group 99 and enter 99.06–99.11 from the nameplate. Leave 99.04 on Scalar unless the load needs vector control.

4

Select the macro

Open group 96, set 96.04 Macro select to 3-wire, and confirm 96.05 Macro active shows the same name. Every non-motor parameter now returns to the macro defaults.

5

Check the I/O mapping

Open the parameters in the table below and confirm each one points to the input shown. Change only what your wiring differs on.

6

Tune ramps, presets and limits

Set acceleration and deceleration times, preset speeds or setpoints, and min/max limits in group 30 (30.11–30.14).

7

Test with the Monitor window

Add 01.06 Output frequency, 01.07 Motor current, 10.02 DI delayed status and 12.12 AI1 scaled value. Operate each switch and watch the matching bit and value change.

8

Save and document

Write 96.07 Parameter save manually = Save, then use Print to keep a PDF parameter record (as on the Softwell lab printouts). In pro, compare against the backup to list every change.

Expected result: 96.05 Macro active shows 3-wire, every row in the check table matches, and each switch changes the matching bit in 10.02 DI delayed status.

Check after selecting

ParameterNameShould read
20.01Ext1 commands3-wire start / stop / direction
20.03Ext1 in1 sourceDI1 (start pulse)
20.04Ext1 in2 sourceDI2 (stop pulse)
20.05Ext1 in3 sourceDI3 (direction)
28.22 / 28.23Constant frequency sel1 / sel2DI4 / DI5
28.11Ext1 frequency ref1AI1 scaled
Alternate96.04 = Alternate

One input starts the motor forward, another starts it in reverse, and a run-enable input can stop it at any time.

Control terminals X1–X3 · Alternate macro (inputs that change most are highlighted)

2AI1Speed / frequency reference 1, 0–10 V
5AI2Not configured
13DI1Start forward (DI1 = DI2 → stop)
14DI2Start reverse
15DI3Constant speed / frequency select
16DI4Constant speed / frequency select
17DI5Ramp set 1 (0) / Ramp set 2 (1)
18DI6Run enable; 0 stops the drive

Wiring diagram

Control terminalsField devicesFunction in this macro2AI1Speed / frequency reference 1, 0–10 V3AGNDAnalog common4+10V10 V reference5AI2Not configured6AGNDAnalog common7AO1Output frequency, 0–20 mA8AO2Motor current, 0–20 mA9AGNDAnalog common10+24V24 V DC aux, max 250 mA11DGND24 V common12DCOMDigital input common13DI1Start forward (DI1 = DI2 → stop)14DI2Start reverse15DI3Constant speed / frequency select16DI4Constant speed / frequency select17DI5Ramp set 1 (0) / Ramp set 2 (1)18DI6Run enable; 0 stops the drive19–21RO1Ready run22–24RO2Running25–27RO3Fault (-1)factory jumper10 kΩ speed potRun forwardRun reversePreset select APreset select BRamp selectRun enable (permissive)
Wiring for the Alternate macro. Digital inputs are fed from the drive’s own +24 V (terminal 10) with DGND–DCOM bridged by the factory jumper. Set S1 to U for 0–10 V on AI1 and S2 to I for 4–20 mA on AI2, matching 12.15 and 12.25.

Configure the Alternate macro in Drive Composer

Drive Composer entry / pro
0 of 8 steps done
Before you start
  • ACS580 powered, STO terminals closed (factory jumpers in place)
  • PC with Drive Composer and a USB cable to the assistant control panel
  • Motor nameplate data and the wiring done as in the diagram
1

Connect

Plug a USB cable from the PC into the USB port on the drive's assistant control panel, open Drive Composer (entry or pro) and connect. The drive appears in the drive list.

2

Back up first

Save the current parameters to a file (entry) or take a full Backup (pro) so you can return to the old setup.

3

Enter motor data

Open Parameters › group 99 and enter 99.06–99.11 from the nameplate. Leave 99.04 on Scalar unless the load needs vector control.

4

Select the macro

Open group 96, set 96.04 Macro select to Alternate, and confirm 96.05 Macro active shows the same name. Every non-motor parameter now returns to the macro defaults.

5

Check the I/O mapping

Open the parameters in the table below and confirm each one points to the input shown. Change only what your wiring differs on.

6

Tune ramps, presets and limits

Set acceleration and deceleration times, preset speeds or setpoints, and min/max limits in group 30 (30.11–30.14).

7

Test with the Monitor window

Add 01.06 Output frequency, 01.07 Motor current, 10.02 DI delayed status and 12.12 AI1 scaled value. Operate each switch and watch the matching bit and value change.

8

Save and document

Write 96.07 Parameter save manually = Save, then use Print to keep a PDF parameter record (as on the Softwell lab printouts). In pro, compare against the backup to list every change.

Expected result: 96.05 Macro active shows Alternate, every row in the check table matches, and each switch changes the matching bit in 10.02 DI delayed status.

Check after selecting

ParameterNameShould read
20.03Ext1 in1 sourceDI1 (start forward)
20.04Ext1 in2 sourceDI2 (start reverse)
20.12Run enable 1 sourceDI6
28.22 / 28.23Constant frequency sel1 / sel2DI3 / DI4
28.71Freq ramp set selectionDI5
28.11Ext1 frequency ref1AI1 scaled
Motor potentiometer96.04 = Motor potentiometer

Speed goes up and down with two push-buttons or two PLC digital outputs, so no analog reference is needed.

Control terminals X1–X3 · Motor potentiometer macro (inputs that change most are highlighted)

2AI1Not configured
5AI2Not configured
13DI1Stop (0) / Start (1)
14DI2Forward (0) / Reverse (1)
15DI3Reference up
16DI4Reference down
17DI5Constant frequency / speed 1
18DI6Run enable; 0 stops the drive

Wiring diagram

Control terminalsField devicesFunction in this macro2AI1Not configured3AGNDAnalog common4+10V10 V reference5AI2Not configured6AGNDAnalog common7AO1Output frequency, 0–20 mA8AO2Motor current, 0–20 mA9AGNDAnalog common10+24V24 V DC aux, max 250 mA11DGND24 V common12DCOMDigital input common13DI1Stop (0) / Start (1)14DI2Forward (0) / Reverse (1)15DI3Reference up16DI4Reference down17DI5Constant frequency / speed 118DI6Run enable; 0 stops the drive19–21RO1Ready run22–24RO2Running25–27RO3Fault (-1)factory jumperRun switchFwd / Rev switchSpeed up buttonSpeed down buttonPreset speedRun enable (permissive)
Wiring for the Motor potentiometer macro. Digital inputs are fed from the drive’s own +24 V (terminal 10) with DGND–DCOM bridged by the factory jumper. Set S1 to U for 0–10 V on AI1 and S2 to I for 4–20 mA on AI2, matching 12.15 and 12.25.

Configure the Motor potentiometer macro in Drive Composer

Drive Composer entry / pro
0 of 8 steps done
Before you start
  • ACS580 powered, STO terminals closed (factory jumpers in place)
  • PC with Drive Composer and a USB cable to the assistant control panel
  • Motor nameplate data and the wiring done as in the diagram
1

Connect

Plug a USB cable from the PC into the USB port on the drive's assistant control panel, open Drive Composer (entry or pro) and connect. The drive appears in the drive list.

2

Back up first

Save the current parameters to a file (entry) or take a full Backup (pro) so you can return to the old setup.

3

Enter motor data

Open Parameters › group 99 and enter 99.06–99.11 from the nameplate. Leave 99.04 on Scalar unless the load needs vector control.

4

Select the macro

Open group 96, set 96.04 Macro select to Motor potentiometer, and confirm 96.05 Macro active shows the same name. Every non-motor parameter now returns to the macro defaults.

5

Check the I/O mapping

Open the parameters in the table below and confirm each one points to the input shown. Change only what your wiring differs on.

6

Tune ramps, presets and limits

Set acceleration and deceleration times, preset speeds or setpoints, and min/max limits in group 30 (30.11–30.14).

7

Test with the Monitor window

Add 01.06 Output frequency, 01.07 Motor current, 10.02 DI delayed status and 12.12 AI1 scaled value. Operate each switch and watch the matching bit and value change.

8

Save and document

Write 96.07 Parameter save manually = Save, then use Print to keep a PDF parameter record (as on the Softwell lab printouts). In pro, compare against the backup to list every change.

Expected result: 96.05 Macro active shows Motor potentiometer, every row in the check table matches, and each switch changes the matching bit in 10.02 DI delayed status.

Check after selecting

ParameterNameShould read
20.03 / 20.04Ext1 in1 / in2 sourceDI1 / DI2
22.71Motor potentiometer functionEnabled
22.73Motor potentiometer up sourceDI3
22.74Motor potentiometer down sourceDI4
20.12Run enable 1 sourceDI6
22.75Motor potentiometer ramp time40 s default
Hand/Auto96.04 = Hand/Auto

Two external control places, each with its own start, direction and analog reference, and one input that switches between them.

Control terminals X1–X3 · Hand/Auto macro (inputs that change most are highlighted)

2AI1Analog reference for one control place
5AI2Analog reference for the other control place
13DI1Start/stop, Hand
14DI2Direction, Hand
15DI3Hand or Auto selection
16DI4Run enable
17DI5Direction, Auto
18DI6Start/stop, Auto

Wiring diagram

Control terminalsField devicesFunction in this macro2AI1Analog reference for one control place3AGNDAnalog common4+10V10 V reference5AI2Analog reference for the other control place6AGNDAnalog common7AO1Output frequency, 0–20 mA8AO2Motor current, 0–20 mA9AGNDAnalog common10+24V24 V DC aux, max 250 mA11DGND24 V common12DCOMDigital input common13DI1Start/stop, Hand14DI2Direction, Hand15DI3Hand or Auto selection16DI4Run enable17DI5Direction, Auto18DI6Start/stop, Auto19–21RO1Ready run22–24RO2Running25–27RO3Fault (-1)factory jumperHand speed potPLC AO+−Auto reference (PLC AO)Hand runHand Fwd / RevHand / Auto selectorRun enable (permissive)PLCAuto Fwd / Rev (PLC DO)PLCAuto run (PLC DO)
Wiring for the Hand/Auto macro. Digital inputs are fed from the drive’s own +24 V (terminal 10) with DGND–DCOM bridged by the factory jumper. Set S1 to U for 0–10 V on AI1 and S2 to I for 4–20 mA on AI2, matching 12.15 and 12.25.

Configure the Hand/Auto macro in Drive Composer

Drive Composer entry / pro
0 of 8 steps done
Before you start
  • ACS580 powered, STO terminals closed (factory jumpers in place)
  • PC with Drive Composer and a USB cable to the assistant control panel
  • Motor nameplate data and the wiring done as in the diagram
1

Connect

Plug a USB cable from the PC into the USB port on the drive's assistant control panel, open Drive Composer (entry or pro) and connect. The drive appears in the drive list.

2

Back up first

Save the current parameters to a file (entry) or take a full Backup (pro) so you can return to the old setup.

3

Enter motor data

Open Parameters › group 99 and enter 99.06–99.11 from the nameplate. Leave 99.04 on Scalar unless the load needs vector control.

4

Select the macro

Open group 96, set 96.04 Macro select to Hand/Auto, and confirm 96.05 Macro active shows the same name. Every non-motor parameter now returns to the macro defaults.

5

Check the I/O mapping

Open the parameters in the table below and confirm each one points to the input shown. Change only what your wiring differs on.

6

Tune ramps, presets and limits

Set acceleration and deceleration times, preset speeds or setpoints, and min/max limits in group 30 (30.11–30.14).

7

Test with the Monitor window

Add 01.06 Output frequency, 01.07 Motor current, 10.02 DI delayed status and 12.12 AI1 scaled value. Operate each switch and watch the matching bit and value change.

8

Save and document

Write 96.07 Parameter save manually = Save, then use Print to keep a PDF parameter record (as on the Softwell lab printouts). In pro, compare against the backup to list every change.

Expected result: 96.05 Macro active shows Hand/Auto, every row in the check table matches, and each switch changes the matching bit in 10.02 DI delayed status.

Check after selecting

ParameterNameShould read
19.11Ext1/Ext2 selectionDI3
20.03 / 20.04Hand start / direction sourcesDI1 / DI2
20.08 / 20.09Auto start / direction sourcesDI6 / DI5
20.12Run enable 1 sourceDI4
12.15 / 12.25AI1 / AI2 unitMatch S1 / S2 switches
Hand/PID96.04 = Hand/PID

The built-in process PID controller runs the drive, with a second control place for direct speed control by hand.

Control terminals X1–X3 · Hand/PID macro (inputs that change most are highlighted)

2AI1Hand reference or PID setpoint, 0–10 V
5AI2Actual PID feedback, 4–20 mA
13DI1Stop (0) / Start (1), Hand
14DI2Hand (0) / PID (1) selection
15DI3Constant frequency select
16DI4Constant frequency select
17DI5Run enable; 0 stops the drive
18DI6Stop (0) / Start (1), PID

Wiring diagram

Control terminalsField devicesFunction in this macro2AI1Hand reference or PID setpoint, 0–10 V3AGNDAnalog common4+10V10 V reference5AI2Actual PID feedback, 4–20 mA6AGNDAnalog common7AO1Output frequency, 0–20 mA8AO2Motor current, 0–20 mA9AGNDAnalog common10+24V24 V DC aux, max 250 mA11DGND24 V common12DCOMDigital input common13DI1Stop (0) / Start (1), Hand14DI2Hand (0) / PID (1) selection15DI3Constant frequency select16DI4Constant frequency select17DI5Run enable; 0 stops the drive18DI6Stop (0) / Start (1), PID19–21RO1Ready run22–24RO2Running25–27RO3Fault (-1)factory jumperHand speed / PID setpoint pot4–20 mA+−4–20 mA transmitterHand runHand / PID selectorPreset select APreset select BRun enable (permissive)PID run
Wiring for the Hand/PID macro. Digital inputs are fed from the drive’s own +24 V (terminal 10) with DGND–DCOM bridged by the factory jumper. Set S1 to U for 0–10 V on AI1 and S2 to I for 4–20 mA on AI2, matching 12.15 and 12.25.

Configure the Hand/PID macro in Drive Composer

Drive Composer entry / pro
0 of 8 steps done
Before you start
  • ACS580 powered, STO terminals closed (factory jumpers in place)
  • PC with Drive Composer and a USB cable to the assistant control panel
  • Motor nameplate data and the wiring done as in the diagram
1

Connect

Plug a USB cable from the PC into the USB port on the drive's assistant control panel, open Drive Composer (entry or pro) and connect. The drive appears in the drive list.

2

Back up first

Save the current parameters to a file (entry) or take a full Backup (pro) so you can return to the old setup.

3

Enter motor data

Open Parameters › group 99 and enter 99.06–99.11 from the nameplate. Leave 99.04 on Scalar unless the load needs vector control.

4

Select the macro

Open group 96, set 96.04 Macro select to Hand/PID, and confirm 96.05 Macro active shows the same name. Every non-motor parameter now returns to the macro defaults.

5

Check the I/O mapping

Open the parameters in the table below and confirm each one points to the input shown. Change only what your wiring differs on.

6

Tune ramps, presets and limits

Set acceleration and deceleration times, preset speeds or setpoints, and min/max limits in group 30 (30.11–30.14).

7

Test with the Monitor window

Add 01.06 Output frequency, 01.07 Motor current, 10.02 DI delayed status and 12.12 AI1 scaled value. Operate each switch and watch the matching bit and value change.

8

Save and document

Write 96.07 Parameter save manually = Save, then use Print to keep a PDF parameter record (as on the Softwell lab printouts). In pro, compare against the backup to list every change.

Expected result: 96.05 Macro active shows Hand/PID, every row in the check table matches, and each switch changes the matching bit in 10.02 DI delayed status.

Check after selecting

ParameterNameShould read
19.11Ext1/Ext2 selectionDI2 (Hand / PID)
20.03Hand start sourceDI1
20.08PID start sourceDI6
20.12Run enable 1 sourceDI5
40.08Set 1 feedback 1 sourceAI2 percent
40.16Set 1 setpoint 1 sourceAI1 percent
PID96.04 = PID

For applications that always run under PID control, with the setpoint coming from analog input AI1.

Control terminals X1–X3 · PID macro (inputs that change most are highlighted)

2AI1PID setpoint, 0–10 V
5AI2Actual PID feedback, 4–20 mA
13DI1Stop (0) / Start (1), PID
14DI2Constant PID setpoint 1 (40.21)
15DI3Constant PID setpoint 2 (40.22)
16DI4Constant frequency 1 (28.26)
17DI5Run enable; 0 stops the drive
18DI6Not configured

Wiring diagram

Control terminalsField devicesFunction in this macro2AI1PID setpoint, 0–10 V3AGNDAnalog common4+10V10 V reference5AI2Actual PID feedback, 4–20 mA6AGNDAnalog common7AO1Output frequency, 0–20 mA8AO2Motor current, 0–20 mA9AGNDAnalog common10+24V24 V DC aux, max 250 mA11DGND24 V common12DCOMDigital input common13DI1Stop (0) / Start (1), PID14DI2Constant PID setpoint 1 (40.21)15DI3Constant PID setpoint 2 (40.22)16DI4Constant frequency 1 (28.26)17DI5Run enable; 0 stops the drive18DI6Not configured19–21RO1Ready run22–24RO2Running25–27RO3Fault (-1)factory jumperPID setpoint pot4–20 mA+−4–20 mA transmitterPID runFixed setpoint 1Fixed setpoint 2Constant frequency 1Run enable (permissive)
Wiring for the PID macro. Digital inputs are fed from the drive’s own +24 V (terminal 10) with DGND–DCOM bridged by the factory jumper. Set S1 to U for 0–10 V on AI1 and S2 to I for 4–20 mA on AI2, matching 12.15 and 12.25.

Configure the PID macro in Drive Composer

Drive Composer entry / pro
0 of 8 steps done
Before you start
  • ACS580 powered, STO terminals closed (factory jumpers in place)
  • PC with Drive Composer and a USB cable to the assistant control panel
  • Motor nameplate data and the wiring done as in the diagram
1

Connect

Plug a USB cable from the PC into the USB port on the drive's assistant control panel, open Drive Composer (entry or pro) and connect. The drive appears in the drive list.

2

Back up first

Save the current parameters to a file (entry) or take a full Backup (pro) so you can return to the old setup.

3

Enter motor data

Open Parameters › group 99 and enter 99.06–99.11 from the nameplate. Leave 99.04 on Scalar unless the load needs vector control.

4

Select the macro

Open group 96, set 96.04 Macro select to PID, and confirm 96.05 Macro active shows the same name. Every non-motor parameter now returns to the macro defaults.

5

Check the I/O mapping

Open the parameters in the table below and confirm each one points to the input shown. Change only what your wiring differs on.

6

Tune ramps, presets and limits

Set acceleration and deceleration times, preset speeds or setpoints, and min/max limits in group 30 (30.11–30.14).

7

Test with the Monitor window

Add 01.06 Output frequency, 01.07 Motor current, 10.02 DI delayed status and 12.12 AI1 scaled value. Operate each switch and watch the matching bit and value change.

8

Save and document

Write 96.07 Parameter save manually = Save, then use Print to keep a PDF parameter record (as on the Softwell lab printouts). In pro, compare against the backup to list every change.

Expected result: 96.05 Macro active shows PID, every row in the check table matches, and each switch changes the matching bit in 10.02 DI delayed status.

Check after selecting

ParameterNameShould read
20.03Ext1 in1 sourceDI1
40.19 / 40.20Internal setpoint sel1 / sel2DI2 / DI3
40.21 / 40.22Internal setpoint 1 / 2Your fixed setpoints
40.08Set 1 feedback 1 sourceAI2 percent
40.16Set 1 setpoint 1 sourceAI1 percent
20.12Run enable 1 sourceDI5

Wire this macro on a real ACS580

Every macro, Drive Composer, then Modbus RTU and Profinet with a Siemens PLC. Pune classroom or online.

Book a Free Demo Class

Tools: parameter finder and calculators

All parameters from the eight macro guides in one searchable list.

ParameterNameValue or noteUse
12.15 / 12.17–12.20AI1 unit, min, max, scalingV, 0–10 V → 0–50 HzABB standard
12.15 / 12.25AI1 / AI2 unitMatch S1 / S2 switchesHand/Auto
12.15 · 12.25 · 13.15AI1, AI2, AO1 unit (V or mA)Match the S1–S3 switchesABB standard
19.11Ext1/Ext2 selectionDI3Hand/Auto
19.11Ext1/Ext2 selectionDI3 in this macroHand/Auto
19.11Ext1/Ext2 selectionDI2 (Hand / PID)Hand/PID
20.01Ext1 commands3-wire start / stop / direction3-wire
20.01Ext1 commandsSet by the macro for 3-wire start/stop3-wire
20.01 / 20.06Ext1 / Ext2 commandsHand and Auto start sourcesHand/Auto
20.03Ext1 in1 sourceDI1ABB standard
20.03Ext1 in1 sourceDI1ABB standard (vector)
20.03Ext1 in1 sourceDI1 (start pulse)3-wire
20.03Ext1 in1 sourceDI1 (start forward)Alternate
20.03Hand start sourceDI1Hand/PID
20.03Ext1 in1 sourceDI1PID
20.03 / 20.04Ext1 in1 / in2 sourceDI1 / DI2Motor potentiometer
20.03 / 20.04Hand start / direction sourcesDI1 / DI2Hand/Auto
20.04Ext1 in2 sourceDI2ABB standard
20.04Ext1 in2 sourceDI2ABB standard (vector)
20.04Ext1 in2 sourceDI2 (stop pulse)3-wire
20.04Ext1 in2 sourceDI2 (start reverse)Alternate
20.05Ext1 in3 sourceDI3 (direction)3-wire
20.08PID start sourceDI6Hand/PID
20.08 / 20.09Auto start / direction sourcesDI6 / DI5Hand/Auto
20.12Run enable 1 sourceDI6Alternate
20.12Run enable 1 sourceDI6 in this macroAlternate
20.12Run enable 1 sourceDI6Motor potentiometer
20.12Run enable 1 sourceDI4Hand/Auto
20.12Run enable 1 sourceDI4 in this macroHand/Auto
20.12Run enable 1 sourceDI5Hand/PID
20.12Run enable 1 sourceDI5PID
22.11Ext1 speed ref1AI1 scaledABB standard (vector)
22.22 / 22.23Constant speed sel1 / sel2DI3 / DI4ABB standard (vector)
22.26 / 22.27 / 22.28Constant speed 1 / 2 / 3DI3–DI4 = 10 / 01 / 11ABB standard (vector)
22.26–22.28Constant speed 1–3 (vector)Same DI pattern3-wire
22.71Motor potentiometer functionEnabledMotor potentiometer
22.71Motor potentiometer functionEnabled by the macroMotor potentiometer
22.73Motor potentiometer up sourceDI3Motor potentiometer
22.74Motor potentiometer down sourceDI4Motor potentiometer
22.75Motor potentiometer ramp time40 s defaultMotor potentiometer
22.75Motor potentiometer ramp time40 s on the Softwell benchMotor potentiometer
22.76 / 22.77Motor potentiometer min / max−50 / 50 on the benchMotor potentiometer
22.80Motor potentiometer ref actWatch it while pressing up/downMotor potentiometer
23.11Ramp set selectionDI5ABB standard (vector)
23.12 / 23.13Accel / decel time 1DI5 = 0ABB standard (vector)
23.14 / 23.15Accel / decel time 2DI5 = 1ABB standard (vector)
28.11Ext1 frequency ref1AI1 scaledABB standard
28.11Ext1 frequency ref1AI1 scaled3-wire
28.11Ext1 frequency ref1AI1 scaledAlternate
28.22 / 28.23Constant frequency sel1 / sel2DI3 / DI4ABB standard
28.22 / 28.23Constant frequency sel1 / sel2DI4 / DI53-wire
28.22 / 28.23Constant frequency sel1 / sel2DI3 / DI4Alternate
28.26Constant frequency 1Picked by DI4PID
28.26 / 28.27 / 28.28Constant frequency 1 / 2 / 3DI3–DI4 = 10 / 01 / 11ABB standard
28.26–28.28Constant frequency 1–3 (scalar)DI4–DI5 = 10 / 01 / 113-wire
28.26–28.28Constant frequency 1–3DI3–DI4 = 10 / 01 / 11Alternate
28.71Freq ramp set selectionDI5ABB standard
28.71Freq ramp set selectionDI5Alternate
28.72 / 28.73Freq accel / decel time 1DI5 = 0ABB standard
28.72–28.75Ramp set 1 and 2DI5 selectsAlternate
28.74 / 28.75Freq accel / decel time 2DI5 = 1ABB standard
40.08Set 1 feedback 1 sourceAI2 percentHand/PID
40.08Set 1 feedback 1 sourceAI2 percentHand/PID
40.08Set 1 feedback 1 sourceAI2 percentPID
40.08 / 40.16Feedback / setpoint sourceAI2 / AI1 percentPID
40.16Set 1 setpoint 1 sourceAI1 percentHand/PID
40.16Set 1 setpoint 1 sourceAI1 percentHand/PID
40.16Set 1 setpoint 1 sourceAI1 percentPID
40.19 / 40.20Internal setpoint sel1 / sel2DI2 / DI3PID
40.21 / 40.22Internal setpoint 1 / 2Your fixed setpointsPID
40.21 / 40.22Set 1 internal setpoint 1 / 2Picked by DI2 / DI3PID
40.32 / 40.33PID gain / integration time1.00 / 60 s defaultsHand/PID
40.32 / 40.33Gain / integration time1.00 / 60 s defaultsPID
40.43 / 40.44Sleep level / sleep delayFor low-demand periodsHand/PID
96.04Macro selectABB standardABB standard
96.04Macro selectABB standard (vector)ABB standard (vector)
96.04Macro select3-wire3-wire
96.04Macro selectAlternateAlternate
96.04Macro selectMotor potentiometerMotor potentiometer
96.04Macro selectHand/AutoHand/Auto
96.04Macro selectHand/PIDHand/PID
96.04Macro selectPIDPID
99.04Motor control modeScalar by defaultABB standard
99.04Motor control modeVectorABB standard (vector)
99.04Motor control modeScalar by default3-wire
99.04Motor control modeScalar by defaultAlternate
99.04Motor control modeScalar by defaultHand/Auto
99.06–99.11Motor nameplate dataEnter before the ID runABB standard (vector)
99.13ID run requestedStandstill or normalABB standard (vector)

Energy saving calculator (fans and pumps)

For centrifugal loads, power falls with the cube of speed (affinity law). Change the numbers to your own motor, hours and tariff.

Full speed (throttle or damper)
With VFD
Power at this speed
Saving vs full speed
Yearly saving

Estimate only: real savings depend on the system curve, static head and motor efficiency. The drive measures actual savings in group 45.

Ramp-time calculator

ACS580 ramp times are full-scale: the time to go from zero to 50 Hz. Enter yours to see how long the drive takes to reach a target.

50 Hztime

Beyond macros: a real Softwell configuration

On site, many drives start from ABB standard and are then reshaped. In one Softwell parameter sheet used for ACS880, ACS580 and ACS560 dosing and valve drives, control location EXT1 takes start and speed from a PLC over Profinet (20.01 Fieldbus A, 22.11 FB A ref1), EXT2 is a hardwired backup on DI1 with AI1 as reference, and DI3 switches between them through 19.11.

It is the Hand/Auto idea with a fieldbus in place of the Auto wiring, and building it from scratch is one of the day-three exercises in our course.

Frequently asked questions

How many control macros does the ACS580 have?

The ACS580 standard control program manual in our library lists 10: ABB standard, ABB standard (vector), 3-wire, Alternate, Motor potentiometer, Hand/Auto, Hand/PID, PID, Panel PID and PFC. Newer firmware adds more, so check the manual for your version.

Which parameter selects the macro?

96.04 Macro select. 96.05 Macro active shows which one is in use.

Do macros use scalar or vector control?

All macros use scalar control by default except ABB standard (vector). You can switch any macro to vector in Primary settings › Motor › Control mode.

What happens to my settings when I change macro?

Everything except motor data returns to the new macro's defaults and the I/O functions change, so check wiring and back up first.

Get the ABB VFD syllabus + free demo class

Share your details — a Softwell training advisor will call you within 24 hours with batch dates, fees and hardware access options.

No spam. Used only to share course details for this enquiry.

Learn ABB drives on real hardware

Offline 10 AM–2 PM or 2:30–6:30 PM, online 7:30–9 PM, Sunday 11 AM–5 PM. ABB VFD is part of Level 01 with Modbus RTU and Ethernet.

Request Course Details
>